CHAPTER 6: USING THE METER
Note
NOTE
WARNING
Note
NOTE
EPM 2200 POWER METER – INSTRUCTION MANUAL
•
CT Numerator (Primary): 1-9999
•
CT Denominator (Secondary): 1 or 5 (factory set)
•
CT Multiplier: 1, 10, or 100
•
CT Fullscale: Calculation Based on Selections (click Recalculate to view)
•
PT Numerator (Primary): 1-9999
•
PT Denominator (Secondary): 40-600
•
PT Multiplier: 1, 10, 100, or 1000
•
PT Fullscale: Calculation Based on Selections (click Recalculate to view)
•
System Wiring: 3 Element Wye; 2.5 Element Wye; 2 CT Delta
•
Phases Displayed: A, AB, or ABC
VOLTS FULL SCALE = PT Numerator x PT Multiplier
You must specify Primary and Secondary Voltage in Full Scale. Do not use ratios! The PT
Denominator should be the Secondary Voltage level.
Example:
A 14400/120 PT would be entered as:
PT Num: 1440
PT Denom: 120
Multiplier: 10
This example would display a 14.40kV.
Example CT Settings:
200/5 Amps: Set the Ct-n value for 200, Ct-Multiplier value for 1.
800/5 Amps: Set the Ct-n value for 800, Ct-Multiplier value for 1.
2,000/5 Amps: Set the Ct-n value for 2000, Ct-Multiplier value for 1.
10,000/5 Amps: Set the Ct-n value for 1000, Ct-Multiplier value for 10.
Example PT Settings:
277/277 Volts Pt-n value is 277, Pt-d value is 277, Pt-Multiplier is 1.
14,400/120 Volts: Pt-n value is 1440, Pt-d value is 120, Pt-Multiplier value is 10.
138,000/69 Volts: Pt-n value is 1380, Pt-d value is 69, Pt-Multipier value is 100.
345,000/115 Volts: Pt-n value is 3470, Pt-d value is 115, Pt-Multiplier value is 100
345,000/69 Volts: Pt-n value is 345, Pt-d value is 69, Pt-Multiplier value is 1000.
Settings are the same for Wye and Delta configurations.
ENERGY AND DISPLAY
The settings on this screen determine the display configuration of the meter
faceplate.
GE COMMUNICATOR PROGRAMMING OVERVIEW
6–21