CONSIDERATIONS WHEN INSTALLING METERS
4.1.4
Voltage and Power Supply Connections
Power supply
inputs
Voltage
inputs
4.1.5
Ground Connections
4.1.6
Voltage Fuses
4–6
Voltage Inputs are connected to the back of the unit via a optional wire connectors. The
connectors accommodate up to AWG#12 / 2.5 mm wire.
The EPM 2200 ground terminals (
protective earth ground. Use 2.5 mm wire for this connection.
GE requires the use of fuses on each of the sense Voltages and on the control power.
• Use a 0.1 Amp fuse on each voltage input.
• Use a 3.0 Amp fuse on the Power Supply.
Figure 4-4: Voltage Connection
) should be connected directly to the installation's
EPM 2200 POWER METER – INSTRUCTION MANUAL
CHAPTER 4: ELECTRICAL INSTALLATION
RS485 outputs
(do not place voltage
on these terminals!)