CONFIGURATION
PARAMETERS

Basic Configuration

Figure 5-3. Tank Geometry
Product Level
Figure 5-4. Upper Reference
Point
Upper Reference Point
PRELIMINARY
The Rosemount 3308 transmitter can be configured for level, volume,
interface level, and interface distance measurements.
The Rosemount 3308 transmitter can be pre-configured according to the
ordering specifications in the Configuration Data Sheet.
The basic transmitter configuration includes setting the tank geometry
parameters. For interface measurements the dielectric constant of the top
liquid must also be given. For some applications with heavy vapor, the vapor
dielectric must be given as well.
Interface
Level
For the different tank connections the Upper Reference Point is located at the
underside of the threaded adapter or at the underside of the welded flange, as
illustrated in Figure 5-4:
Adapter
NPT
Upper Reference Point
Upper Null Zone
URV
LRV
Lower Reference Point
BSP (G)
FLANGE
Rosemount 3308
Probe
Tank Height
Length
5-3