Configuration Specifications; Configuration Tool; Configuration Parameters (Examples); Output Variables And Units - Emerson Rosemount 2240S Reference Manual

Multi-input temperature transmitter
Hide thumbs Also See for Rosemount 2240S:
Table of Contents

Advertisement

Specifications and Reference Data
October 2017
A.3 Configuration specifications
A.3.1 Configuration tool
TankMaster WinSetup is the recommended tool for easy
configuration of Rosemount 2240S. The Tankbus
autoconfiguration feature, handled by the Rosemount 2410 Tank
Hub, supports Rosemount 2240S.
A.3.2 Configuration parameters (examples)
Temperature
Number of temperature sensor elements
Temperature element type (spot or average)
Temperature element position in tank
Water Level Sensor
Level offset (difference between tank zero level and water zero
level)
Probe length (autoconfigured by Rosemount 765)
A.3.3 Output variables and units
Spot and average temperature: °C (Celsius), and °F (Fahrenheit)
Free water level (FWL): meter, centimeter, millimeter, feet, or inch
A.4 F
fieldbus characteristics
OUNDATION
A.4.1 Polarity sensitive
No
A.4.2 Quiescent current draw
30 mA
A.4.3 Lift-off minimum voltage
9.0 VDC
A.4.4 Device capacitance / inductance
See
"Product Certifications" on page 149
A.4.5 Class (Basic or Link Master)
Link Master (LAS)
A.4.6 Number of available VCRs
Maximum 20, including one fixed
A.4.7 Links
Maximum 40
142
A.4.8 Minimum slot time/maximum response
delay/minimum intermessage delay
8 / 5 / 8
A.4.9 Blocks and Execution time
1 Resource block,
3 Transducer blocks (Temperature, Register, AVG_Temp),
2 Multiple Analog Input (MAI) blocks: 15 ms,
6 Analog Input (AI) blocks: 10 ms,
1 Analog Output (AO) block: 10 ms,
1 Signal Characterizer (SGCR) blocks: 10 ms,
1 Proportional/Integral/Derivate (PID) block: 15 ms,
1 Integrator (INT) block: 10 ms
1 Arithmetic (ARTH) block: 10 ms,
2 Input Selector (ISEL) block: 10 ms
1 Control Selector (CS) block: 10 ms,
1 Output Splitter (OS) block: 10 ms
For more information, see the Foundation™ fieldbus Blocks
manual (document no. 00809-0100-4783)
A.4.10 Instantiation
Yes
A.4.11 Conforming F
ITK 6
A.4.12 Field Diagnostics support
Yes
A.4.13 Action support wizards
Restart/stop measurement, write protect device, factory reset -
measurement configuration, reset statistics, start/stop device
simulation
A.4.14 Advanced diagnostics
Failures/Out of specification/Maintenance required alerts:
Software, memory/database, electronics, internal
communication, simulation, auxiliary device, auxiliary device
measurement, ambient temperature, average temperature
measurement, temperature measurement, configuration
Reference Manual
00809-0100-2240, Rev DA
fieldbus
OUNDATION
Specifications and Reference Data