Rosemount 3308
4-14
PRELIMINARY
Coaxial
L > 49 in.
(1250 mm)
Maximum shortening
23.6 in. (600 mm)
Minimum probe length
15.7 in. (400 mm)
L  49 in.
(1250 mm)
To cut a coaxial probe do the
following:
Centering piece
1. Insert the centering piece.
2. Cut the tube to the desired length.
3. Move the centering piece.
4. Cut the rod inside the tube. Make
• Pipes longer than
• Pipes shorter than
5. Update the transmitter
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
(The centering piece is
delivered from factory and
should be used to prevent the
spacers centering the rod from
coming loose).
sure that the rod is fixed with the
centering piece while cutting.
49 in. (1250 mm) can be
shortened by as much as
23.6 in. (600 mm).
49 in. (1250 mm) can be cut as
long as the remaining length is not
less than
15.7 in. (400 mm).
configuration to the new probe
length, see "Probe Length" on
page 5-9.