Combined Operation Mode 1 (Operation Using Both External Start Signal And Control Panel) - Mitsubishi Electric FR-E 500 Instruction Manual

Hide thumbs Also See for FR-E 500:
Table of Contents

Advertisement

3.3.4 Combined operation mode 1 (Operation using both external
start signal and control panel)
When the start signal is provided externally (switch etc.) and the running frequency is
set from the control panel (Pr. 79 = 3).
The external frequency setting signal and PU's forward rotation, reverse rotation and
STOP
keys are not accepted. (Note)
RESET
Operation command: externally connected start signal
Frequency setting:
Step
Power on
Switch power on.
1
Operation mode selection
Refer to page 52 and set "3" in Pr. 79 "operation mode
selection".
2
The [PU] and [EXT] indications are lit.
Start
Turn on the start switch (STF or STR).
Note: The motor does not start if both the forward and
reverse rotation switches are turned on. If both
3
switches are turned on during operation, the motor
decelerates to a stop.
The [RUN] indication is lit to indicate forward
rotation, or flickers to indicate reverse rotation.
Running frequency setting
Set the running frequency to 60.00Hz with the
key.
4
Stop
Turn off the start switch (STF or STR).
The motor stops.
The [RUN] indication goes off.
5
STOP
Note: The
key is made valid if any of "14" to "17" is set in Pr. 75 "PU stop
RESET
selection".
/
key of the control panel (FR-PA02-
command (multi-speed command has priority) Refer to page 72.
Description
/
58
) or multi-speed
02
Image
ON
Flicker
Forward rotation
Reverse
rotation
Hz
RUN
ON
A
MON
PU
EXT
<Step setting>
Hz
RUN
A
MON
PU
EXT

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e 520s ecFr-e 540 ec

Table of Contents