SAFETY INSTRUCTIONS
1. Electric Shock Prevention
! While power is on or when the inverter is running, do not open the front cover.
You may get an electric shock.
! Do not run the inverter with the front cover removed. Otherwise, you may access
the exposed high-voltage terminals or the charging part of the circuitry and get
an electric shock.
! If power is off, do not remove the front cover except for wiring or periodic
inspection. You may access the charged inverter circuits and get an electric
shock.
! Before starting wiring or inspection, switch power off, wait for more than 10
minutes, and check for residual voltage with a meter (refer to chapter 2 for
further details) etc.
! Earth the Inverter.
! Any person who is involved in the wiring or inspection of this equipment should
be fully competent to do the work.
! Always install the inverter before wiring. Otherwise, you may get an electric
shock or be injured.
! Operate the switches and potentiometers with dry hands to prevent an electric
shock.
! Do not subject the cables to scratches, excessive stress, heavy loads or
pinching. Otherwise, you may get an electric shock.
! Do not change the cooling fan while power is on.
It is dangerous to change the cooling fan while power is on.
2. Fire Prevention
! Mount the inverter and brake resistor on an incombustible surface. Installing the
inverter directly on or near a combustible surface could lead to a fire.
! If the inverter has become faulty, switch off the inverter power. A continuous flow
of large current could cause a fire.
! When a brake resistor is used, use an alarm signal to switch power off.
Otherwise, the brake resistor will overheat abnormally due a brake transistor or
other fault, resulting in a fire.
! Do not connect a resistor directly to the DC terminals +, −. This could cause a
fire.
WARNING
CAUTION
A - 2

Hide quick links: