Mitsubishi Electric FR-E 500 Instruction Manual page 180

Hide thumbs Also See for FR-E 500:
Table of Contents

Advertisement

Operation Panel Indication
Name
Description
Check point
Corrective action
Operation Panel Indication
Name
Description
Check point
Corrective action
Operation Panel Indication
Name
Description
Check point
Corrective action
Operation Panel Indication
Name
Description
Check point
Corrective action
E. OC3
Overcurrent shut-off during deceleration
When the inverter output current reaches or exceeds
approximately 200% of the rated current during deceleration
(other than acceleration or constant speed), the protective
circuit is activated to stop the inverter output.
Check for sudden speed reduction.
Check for output short-circuit/ground fault.
Check for too fast operation of motor's mechanical brake.
Increase the deceleration time.
Adjust brake operation.
E. OV1
Regenerative overvoltage shut-off during acceleration
If regenerative energy causes the inverter's internal main
circuit DC voltage to reach or exceed the specified value, the
protective circuit is activated to stop the inverter output. It
may also be activated by a surge voltage generated in the
power supply system.
Check for too slow acceleration.
Decrease the acceleration time.
E. OV2
Regenerative overvoltage shut-off during constant speed
If regenerative energy causes the inverter's internal main
circuit DC voltage to reach or exceed the specified value, the
protective circuit is activated to stop the inverter output.
It may also be activated by a surge voltage generated in the
power supply system.
Check for sudden load change.
Keep load stable.
• Use the brake unit or high power factor converter (FR-HC)
as required.
E. OV3
Regenerative overvoltage shut-off during deceleration or stop
If regenerative energy causes the inverter's internal main
circuit DC voltage to reach or exceed the specified value, the
protective circuit is activated to stop the inverter output.
It may also be activated by a surge voltage generated in the
power supply system.
Check for sudden speed reduction.
• Increase the deceleration time. (Set the deceleration time
which matches the inertia moment of the load.)
• Decrease the braking duty.
• Use the brake unit or high power factor converter (FR-HC)
as required.
164
PROTECTIVE FUNCTIONS
FR-PU04
OC During Dec
FR-PU04
OV During Acc
FR-PU04
Stedy Spd OV
FR-PU04
OV During Dec
5