<Operation procedure>
! When using the control panel (FR-PA02-
1) Select the PU operation mode.
2) Set the running frequency.
3) Press the
key.
SET
4) Read Pr. 901 "AM terminal calibration".
5) Press the
key to run the inverter. (Motor need not be connected.)
FWD
6) Hold down the
(Depending on the setting, it may take some time until the pointer moves.)
7) Press the
key for about 1.5 s.
SET
STOP
8) Press the
RESET
REMARKS
Calibration can also be made for external operation. Set the frequency in the external
operation mode and make calibration in the steps 4) to 8).
Note: It is possible to calibrate even during operation.
/
key to adjust the meter pointer to a required position.
key to stop the inverter.
)