Advertisement

5 SETTINGS
UR-1
SETTING
TELEPROT OUTPUT 1-1:
(same for 1-2...1-16)
Off (Flexlogic Operand)
SETTING
TELEPROT INPUT 1-1
DEFAULT:
(same for 1-2...1-16)
FLEXLOGIC OPERAND
On
TELEPRO INPUT 1-1 On
Off
OR
(same for 1-2...1-16)
SETTING
TELEPROT OUTPUT 2-1:
(same for 1-2...1-16)
Off (Flexlogic Operand)
SETTING
TELEPROT INPUT 2-1
DEFAULT:
(same for 1-2...1-16)
FLEXLOGIC OPERAND
On
TELEPRO INPUT 2-1 On
Off
OR
(same for 1-2...1-16)
Figure 5–136: TELEPROTECTION INPUT/OUTPUT PROCESSING
PATH: SETTINGS
INPUTS/OUTPUTS
GOOSE ANALOG
INPUT 1
MESSAGE
MESSAGE
MESSAGE
The IEC 61850 GOOSE analog inputs feature allows the transmission of analog values between any two UR-series
devices. The following settings are available for each GOOSE analog input.
ANALOG 1 DEFAULT: This setting specifies the value of the GOOSE analog input when the sending device is offline
and the
ANALOG 1 DEFAULT MODE
point number. Because of the large range of this setting, not all possible values can be stored. Some values may be
rounded to the closest possible floating point number.
ANALOG 1 DEFAULT MODE: When the sending device is offline and this setting is "Last Known", the value of the
GOOSE analog input remains at the last received value. When the sending device is offline and this setting value is
"Default Value", then the value of the GOOSE analog input is defined by the
GOOSE ANALOG 1 UNITS: This setting specifies a four-character alphanumeric string that can is used in the actual
values display of the corresponding GOOSE analog input value.
GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna-
log™ values in other T60 features, such as FlexElements™. The base factor is applied to the GOOSE analog input
FlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
GE Multilin
ACTUAL VALUES
CHANNEL 1 STATUS:
Communication channel #1
(Teleprotection I/O Enabled)
Fail
OK
ACTUAL VALUES
CHANNEL 2 STATUS:
Communication channel #2
(On 3-terminal system or 2-terminal
with redundant channel)
Fail
OK

IEC 61850 GOOSE ANALOGS

ANALOG
1 DEFAULT:
1000.000
ANALOG
1 DEFAULT
MODE: Default Value
GOOSE ANALOG
1
UNITS:
GOOSE ANALOG
1 PU:
1.000
is set to "Default Value".This setting is stored as an IEEE 754 / IEC 60559 floating
T60 Transformer Protection System
5.8 INPUTS/OUTPUTS
UR-2
ACTUAL VALUES
SETTING
CHANNEL 1 STATUS:
TELEPROT INPUT 1-1
DEFAULT:
(same for 1-2...1-16)
On
Fail
Off
OK
ACTUAL VALUES
SETTING
CHANNEL 2 STATUS:
TELEPROT INPUT 2-1
DEFAULT:
(same for 2-2...2-16)
On
Fail
Off
OK
5.8.12 IEC 61850 GOOSE ANALOGS
GOOSE ANALOG INPUT 1(16)
Range: –1000000.000 to 1000000.000 in steps of 0.001
Range: Default Value, Last Known
Range: up to 4 alphanumeric characters
Range: 0.000 to 1000000000.000 in steps of 0.001
setting.
ANALOG 1 DEFAULT
FLEXLOGIC OPERAND
TELEPRO INPUT 1-1 On
OR
(same for 1-2...1-16)
SETTING
TELEPROT OUTPUT 1-1:
(same for 1-2...1-16)
Off (Flexlogic Operand)
UR-2 or UR-3
FLEXLOGIC OPERAND
TELEPRO INPUT 2-1 On
OR
(same for 2-2...2-16)
SETTING
TELEPROT OUTPUT 2-1:
(same for 2-2...2-16)
Off (Flexlogic Operand)
842750A2.CDR
5