GE t60 Instruction Manual page 315

Ur series transformer protection system
Hide thumbs Also See for t60:
Table of Contents

Advertisement

5 SETTINGS
The equation above brings an advantage of generating the restraining signal of twice the external ground fault current,
while reducing the restraint below the internal ground fault current. The negative-sequence component of the restraining
signal (IR2) is meant to provide maximum restraint during external phase-to-phase faults and is calculated as follows:
The multiplier of 1 is used by the relay for first two cycles following complete de-energization of the winding (all three phase
currents below 5% of nominal for at least five cycles). The multiplier of 3 is used during normal operation; that is, two cycles
after the winding has been energized. The lower multiplier is used to ensure better sensitivity when energizing a faulty
winding.
The positive-sequence component of the restraining signal (IR1) is meant to provide restraint during symmetrical condi-
tions, either symmetrical faults or load, and is calculated according to the following algorithm:
>
1 If
I_1
1.5 pu
of phase CT, then
>
2
If
I_1
I_0
, then
3
else
IR1
=
0
I_1 8 ⁄
4 else
IR1
=
Under load-level currents (below 150% of nominal), the positive-sequence restraint is set to 1/8th of the positive-sequence
current (line 4). This is to ensure maximum sensitivity during low-current faults under full load conditions. Under fault-level
currents (above 150% of nominal), the positive-sequence restraint is removed if the zero-sequence component is greater
than the positive-sequence (line 3), or set at the net difference of the two (line 2).
The raw restraining signal (Irest) is further post-filtered for better performance during external faults with heavy CT satura-
tion and for better switch-off transient control:
where k represents a present sample, k – 1 represents the previous sample, and α is a factory constant (α < 1). The equa-
tion above introduces a decaying memory to the restraining signal. Should the raw restraining signal (Irest) disappear or
drop significantly, such as when an external fault gets cleared or a CT saturates heavily, the actual restraining signal (Igr(k))
will not reduce instantly but will keep decaying decreasing its value by 50% each 15.5 power system cycles.
Having the differential and restraining signals developed, the element applies a single slope differential characteristic with a
minimum pickup as shown in the logic diagram below.
SETTING
RESTD GND FT1
FUNCTION:
Disabled=0
Enabled=1
SETTING
AND
RESTD GND FT1
BLOCK:
Off=0
SETTING
RESTD GND FT1
SOURCE:
IG
Differential
IN
I_0
Restraining
I_1
Currents
I_2
Figure 5–100: RESTRICTED GROUND FAULT SCHEME LOGIC
GE Multilin
IR0
IG IN
IG
=
=
IR2
=
I_2
or IR2
×
(
)
IR1
3
I_1
I_0
=
Igr k ( )
max Irest k ( ) α Igr k 1
(
=
SETTING
RESTD GND FT1
PICKUP:
RUN
Igd > PICKUP
SETTING
RESTD GND FT1
SLOPE:
RUN
Igd
> SLOPE *
Igr
and
ACTUAL VALUES
RGF 1 gd Mag
I
RGF 1 gr Mag
I
T60 Transformer Protection System
(
)
IA
IB
IC
+
+
×
=
3
I_2
,
×
(
)
)
SETTINGS
RESTD GND FT1 PICKUP
DELAY:
RESTD GND FT1 RESET
DELAY:
t PKP
AND
t RST
5.6 GROUPED ELEMENTS
(EQ 5.41)
(EQ 5.42)
(EQ 5.43)
FLEXLOGIC OPERANDS
RESTD GND FT1 PKP
RESTD GND FT1 DPO
RESTD GND FT1 OP
828002A2.CDR
5-183
5

Advertisement

Table of Contents
loading

Table of Contents