This addendum contains information that relates to the T60 Transformer Protection System, version 5.7x. This adden-
dum lists a number of information items that appear in the instruction manual GEK-113531B (revision U3) but are not
included in the current T60 operations.
The following functions and items are not yet available with the current version of the T60 relay:
• Signal sources SRC 5 and SRC 6.
Version 4.0x and higher releases of the T60 relay includes new hardware (CPU and CT/VT modules).
• The new CPU modules are specified with the following order codes: 9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, and 9S.
• The new CT/VT modules are specified with the following order codes: 8F, 8G, 8H, 8J 8L, 8M, 8N, 8R.
The following table maps the relationship between the old CPU and CT/VT modules to the newer versions:
MODULE
OLD
CPU
9A
9C
9D
---
---
---
---
---
---
---
---
CT/VT
8A
8B
8C
8D
--
--
--
--
The new CT/VT modules can only be used with the new CPUs (9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, and 9S), and
the old CT/VT modules can only be used with the old CPU modules (9A, 9C, 9D). To prevent any hardware mis-
matches, the new CPU and CT/VT modules have blue labels and a warning sticker stating "Attn.: Ensure CPU and
DSP module label colors are the same!". In the event that there is a mismatch between the CPU and CT/VT module,
the relay will not function and a
All other input/output modules are compatible with the new hardware.
With respect to the firmware, firmware versions 4.0x and higher are only compatible with the new CPU and CT/VT mod-
ADDENDUM
NEW
DESCRIPTION
9E
RS485 and RS485 (Modbus RTU, DNP)
9G
RS485 and 10Base-F (Ethernet, Modbus TCP/IP, DNP)
9H
RS485 and redundant 10Base-F (Ethernet, Modbus TCP/IP, DNP)
9J
RS485 and multi-mode ST 100Base-FX
9K
RS485 and multi-mode ST redundant 100Base-FX
9L
RS485 and single mode SC 100Base-FX
9M
RS485 and single mode SC redundant 100Base-FX
9N
RS485 and 10/100Base-T
9P
RS485 and single mode ST 100Base-FX
9R
RS485 and single mode ST redundant 100Base-FX
9S
RS485 and six-port managed Ethernet switch
8F
Standard 4CT/4VT
8G
Sensitive ground 4CT/4VT
8H
Standard 8CT
8J
Sensitive ground 8CT
8L
Standard 4CT/4VT with enhanced diagnostics
8M
Sensitive ground 4CT/4VT with enhanced diagnostics
8N
Standard 8CT with enhanced diagnostics
8R
Sensitive ground 8CT with enhanced diagnostics