5 SETTINGS
The GGIO5 integer configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
GGIO5 UINTEGER
CONFIGURATION
MESSAGE
MESSAGE
The GGIO5 logical node allows IEC 61850 client access to integer data values. This allows access to as many as 16
unsigned integer value points, associated timestamps, and quality flags. The method of configuration is similar to that of
GGIO1 (binary status values). The settings allow the selection of FlexInteger™ values for each GGIO5 integer value point.
It is intended that clients use GGIO5 to access generic integer values from the T60. Additional settings are provided to
allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger™ values to the
GGIO5 integer inputs. The following setting is available for all GGIO5 configuration points.
GGIO5 UINT IN 1 VALUE: This setting selects the FlexInteger™ value to drive each GGIO5 integer status value
(GGIO5.ST.UIntIn1). This setting is stored as an 32-bit unsigned integer value.
The report control configuration settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
REPORT 1
CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Changes to the report configuration will not take effect until the T60 is restarted.
Please disconnect any IEC 61850 client connection to the T60 prior to making setting changes to the report config-
uration. Disconnecting the rear Ethernet connection from the T60 will disconnect the IEC 61850 client connection.
NOTE
GE Multilin
COMMUNICATIONS
IEC 61850...
GGIO5 UINT In
1:
Off
GGIO5 UINT In
2:
Off
GGIO5 UINT 1n 16:
Off
COMMUNICATIONS
IEC 61850...
REPORT 1
RptID:
REPORT 1
OptFlds:
0
REPORT 1
BufTm:
0
REPORT 1
TrgOps:
0
REPORT 1
IntgPd:
0
T60 Transformer Protection System
5.2 PRODUCT SETUP
GGIO5 ANALOG CONFIGURATION
Range: Off, any FlexInteger parameter
Range: Off, any FlexInteger parameter
Range: Off, any FlexInteger parameter
REPORT...
REPORT 1(6) CONFIGURATION
Range: up to 66 alphanumeric characters
Range: 0 to 65535 in steps of 1
Range: 0 to 4294967295 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 4294967295 in steps of 1