GE t60 Instruction Manual page 535

Ur series transformer protection system
Hide thumbs Also See for t60:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 48 of 54)
ADDR
REGISTER NAME
Control Pushbuttons (Read/Write Setting) (7 modules)
C760
Control Pushbutton 1 Function
C761
Control Pushbutton 1 Events
C762
...Repeated for Control Pushbutton 2
C764
...Repeated for Control Pushbutton 3
C766
...Repeated for Control Pushbutton 4
C768
...Repeated for Control Pushbutton 5
C76A
...Repeated for Control Pushbutton 6
C76C
...Repeated for Control Pushbutton 7
Clear Records (Read/Write Setting)
C771
Clear User Fault Reports operand
C772
Clear Event Records operand
C773
Clear Oscillography operand
C774
Clear Data Logger operand
C775
Clear Breaker 1 Arcing Current operand
C776
Clear Breaker 2 Arcing Current operand
C777
Clear Breaker 3 Arcing Current operand
C778
Clear Breaker 4 Arcing Current operand
C77B
Clear Demand operand
C77D
Clear Energy operand
C77F
Clear Unauthorized Access operand
C781
Clear Platform Direct Input/Output Statistics operand
C782
Reserved (13 items)
Force Contact Inputs/Outputs (Read/Write Settings)
C7A0
Force Contact Input x State (96 items)
C800
Force Contact Output x State (64 items)
Direct Inputs/Outputs (Read/Write Setting)
C880
Direct Device ID
C881
Direct I/O Channel 1 Ring Configuration Function
C882
Platform Direct I/O Data Rate
C883
Direct I/O Channel 2 Ring Configuration Function
C884
Platform Direct I/O Crossover Function
Direct input/output commands (Read/Write Command)
C888
Direct input/output clear counters command
Direct inputs (Read/Write Setting) (96 modules)
C890
Direct Input 1 Device Number
C891
Direct Input 1 Number
C892
Direct Input 1 Default State
C893
Direct Input 1 Events
C894
...Repeated for Direct Input 2
C898
...Repeated for Direct Input 3
C89C
...Repeated for Direct Input 4
C8A0
...Repeated for Direct Input 5
C8A4
...Repeated for Direct Input 6
C8A8
...Repeated for Direct Input 7
C8AC
...Repeated for Direct Input 8
C8B0
...Repeated for Direct Input 9
C8B4
...Repeated for Direct Input 10
C8B8
...Repeated for Direct Input 11
C8BC
...Repeated for Direct Input 12
C8C0
...Repeated for Direct Input 13
C8C4
...Repeated for Direct Input 14
C8C8
...Repeated for Direct Input 15
C8CC
...Repeated for Direct Input 16
GE Multilin
RANGE
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
---
0 to 2
0 to 3
1 to 16
0 to 1
64 to 128
0 to 1
0 to 1
0 to 1
0 to 16
0 to 96
0 to 3
0 to 1
T60 Transformer Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
---
F001
---
1
F144
---
1
F131
---
1
F001
---
1
F126
kbps
64
F001
---
1
F126
---
1
F102
---
1
F126
---
1
F001
---
1
F001
---
1
F086
---
1
F102
DEFAULT
0 (Disabled)
0 (Disabled)
B
0
0
0
0
0
0
0
0
0
0
0
0
0
0 (Disabled)
0 (Disabled)
1
0 (No)
64
0 (No)
0 (Disabled)
0 (No)
0
0
0 (Off)
0 (Disabled)
B-55

Advertisement

Table of Contents
loading

Table of Contents