Advertisement

5.6 GROUPED ELEMENTS
PATH: SETTINGS
GROUPED ELEMENTS

LOAD ENCROACHMENT

5
The load encroachment element responds to the positive-sequence voltage and current and applies a characteristic shown
in the figure below.
The element operates if the positive-sequence voltage is above a settable level and asserts its output signal that can be
used to block selected protection elements such as distance or phase overcurrent. The following figure shows an effect of
the load encroachment characteristics used to block the quadrilateral distance element.
5-148
SETTING GROUP 1(6)
LOAD ENCROACHMENT
FUNCTION: Disabled
LOAD ENCROACHMENT
MESSAGE
SOURCE: SRC 1
LOAD ENCROACHMENT
MESSAGE
MIN VOLT: 0.250 pu
LOAD ENCROACHMENT
MESSAGE
REACH: 1.00 Ω
LOAD ENCROACHMENT
MESSAGE
ANGLE: 30°
LOAD ENCROACHMENT
MESSAGE
PKP DELAY: 0.000 s
LOAD ENCROACHMENT
MESSAGE
RST DELAY: 0.000 s
LOAD ENCRMNT BLK:
MESSAGE
Off
LOAD ENCROACHMENT
MESSAGE
TARGET: Self-reset
LOAD ENCROACHMENT
MESSAGE
EVENTS: Disabled
–REACH
LOAD ENCROACHMENT
OPERATE
Figure 5–76: LOAD ENCROACHMENT CHARACTERISTIC
T60 Transformer Protection System
LOAD ENCROACHMENT
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.02 to 250.00 ohms in steps of 0.01
Range: 5 to 50° in steps of 1
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: Flexlogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
X
REACH
LOAD ENCROACHMENT
OPERATE
827846A1.CDR
5 SETTINGS
5.6.5 LOAD ENCROACHMENT
R