GE t60 Instruction Manual page 263

Ur series transformer protection system
Hide thumbs Also See for t60:
Table of Contents

Advertisement

5 SETTINGS
c) GROUND DISTANCE
PATH: SETTINGS
GROUPED ELEMENTS
GROUND DISTANCE Z1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
SETTING GROUP 1(6)
DISTANCE
GND DIST Z1
FUNCTION: Disabled
GND DIST Z1 DIR:
Forward
GND DIST Z1
SHAPE: Mho
GND DIST Z1
Z0/Z1 MAG: 2.70
GND DIST Z1
Z0/Z1 ANG: 0°
GND DIST Z1
ZOM/Z1 MAG: 0.00
GND DIST Z1
ZOM/Z1 ANG: 0°
GND DIST Z1
REACH: 2.00 Ω
GND DIST Z1
RCA: 85°
GND DIST Z1 REV
REACH: 2.00 Ω
GND DIST Z1 REV
REACH RCA: 85°
GND DIST Z1 POL
CURRENT: Zero-seq
GND DIST Z1 NON-
HOMOGEN ANG: 0.0°
GND DIST Z1
COMP LIMIT: 90°
GND DIST Z1
DIR RCA: 85°
GND DIST Z1
DIR COMP LIMIT: 90°
GND DIST Z1 QUAD
RGT BLD: 10.00 Ω
GND DIST Z1 QUAD
RGT BLD RCA: 85°
GND DIST Z1 QUAD
LFT BLD: 10.00 Ω
GND DIST Z1 QUAD
LFT BLD RCA: 85°
GND DIST Z1
SUPV: 0.200 pu
T60 Transformer Protection System
5.6 GROUPED ELEMENTS
GROUND DISTANCE Z1(Z3)
Range: Disabled, Enabled
Range: Forward, Reverse, Non-directional
Range: Mho, Quad
Range: 0.00 to 10.00 in steps of 0.01
Range: –90 to 90° in steps of 1
Range: 0.00 to 7.00 in steps of 0.01
Range: –90 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 30 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 30 to 90° in steps of 1
Range: Zero-seq, Neg-seq
Range: –40.0 to 40.0° in steps of 0.1
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 60 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 60 to 90° in steps of 1
Range: 0.050 to 30.000 pu in steps of 0.001
5
5-131