Advertisement

5.7 CONTROL ELEMENTS
PATH: SETTINGS
CONTROL ELEMENTS
SETTING GROUPS
5
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the
settings menu. The faceplate Settings In Use LEDs indicate which active group (with a non-flashing energized
ELEMENTS
LED) is in service.
The
SETTING GROUPS BLK
"On". This can be useful in applications where it is undesirable to change the settings under certain conditions, such as the
breaker being open.
The
GROUP 2 ACTIVATE ON
particular setting group active for use by any grouped element. A priority scheme ensures that only one group is active at a
given time – the highest-numbered group which is activated by its
numbered groups. There is no activate on setting for group 1 (the default active group), because group 1 automatically
becomes active if no other group is active.
The
SETTING GROUP 1 NAME
groups. Once programmed, this name will appear on the second line of the
menu display.
The relay can be set up via a FlexLogic™ equation to receive requests to activate or de-activate a particular non-default
settings group. The following FlexLogic™ equation (see the figure below) illustrates requests via remote communications
(for example,
VIRTUAL INPUT 1 ON
ticular settings group, and requests from several overcurrent pickup measuring elements to inhibit the use of the particular
settings group. The assigned
5-204
SETTINGS GROUPS
SETTING GROUPS
FUNCTION: Disabled
SETTING GROUPS BLK:
MESSAGE
Off
GROUP 2 ACTIVATE ON:
MESSAGE
Off
GROUP 3 ACTIVATE ON:
MESSAGE
Off
GROUP 6 ACTIVATE ON:
MESSAGE
Off
GROUP 1 NAME:
MESSAGE
GROUP 2 NAME:
MESSAGE
GROUP 6 NAME:
MESSAGE
SETTING GROUP
MESSAGE
EVENTS: Disabled
setting prevents the active setting group from changing when the FlexLogic™ parameter is set to
to
GROUP 6 ACTIVATE ON
to
SETTING GROUP 6 NAME
) or from a local contact input (for example,
operand is used to control the "On" state of a particular settings group.
VIRTUAL OUTPUT 1
T60 Transformer Protection System
Range: Disabled, Enabled
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: up to 16 alphanumeric characters
Range: up to 16 alphanumeric characters
Range: up to 16 alphanumeric characters
Range: Disabled, Enabled
settings select a FlexLogic™ operand which, when set, will make the
ACTIVATE ON
settings allows to user to assign a name to each of the six settings
GROUPED ELEMENTS
CONTACT IP 1 ON
5 SETTINGS
5.7.3 SETTING GROUPS
parameter takes priority over the lower-
SETTING GROUP 1(6)
) to initiate the use of a par-
GROUPED
GE Multilin