5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
INSTALLATION
To safeguard against the installation of a relay without any entered settings, the unit will not allow signaling of any output
relay until
RELAY SETTINGS
UNIT NOT PROGRAMMED
The
setting allows the user to uniquely identify a relay. This name will appear on generated reports. This name
RELAY NAME
is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com-
munications channel using the IEC 61850 protocol.
5
5-66
INSTALLATION
RELAY SETTINGS:
Not Programmed
RELAY NAME:
MESSAGE
Relay-1
is set to "Programmed". This setting is defaulted to "Not Programmed" when at the factory. The
self-test error message is displayed until the relay is put into the "Programmed" state.
T60 Transformer Protection System
5.2.19 INSTALLATION
Range: Not Programmed, Programmed
Range: up to 20 alphanumeric characters
5 SETTINGS