Data Logger; Demand - GE t60 Instruction Manual

Ur series transformer management relay
Hide thumbs Also See for t60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP

DATA LOGGER

The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data may
be downloaded to the enerVista UR Setup software and displayed with 'parameters' on the vertical axis and 'time' on the
horizontal axis. All data is stored in non-volatile memory, meaning that the information is retained when power to the relay is
lost.
For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of
channels for a shorter period. The relay automatically partitions the available memory between the channels in use.
5
Changing any setting affecting Data Logger operation will clear any data that is currently in the log.
NOTE
DATA LOGGER RATE: This setting selects the time interval at which the actual value data will be recorded.
DATA LOGGER CHNL 1(16): This setting selects the metering actual value that is to be recorded in Channel 1(16) of
the data log. The parameters available in a given relay are dependent on: the type of relay, the type and number of CT/
VT hardware modules installed, and the type and number of Analog Input hardware modules installed. Upon startup,
the relay will automatically prepare the parameter list. A list of all possible analog metering actual value parameters is
shown in Appendix A: FlexAnalog Parameters. The parameter index number shown in any of the tables is used to
expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the list of
parameters via the relay keypad/display – entering this number via the relay keypad will cause the corresponding
parameter to be displayed.
DATA LOGGER CONFIG: This display presents the total amount of time the Data Logger can record the channels not
selected to "Off" without over-writing old data.
PATH: SETTINGS
PRODUCT SETUP

DEMAND

5-20
DATA LOGGER
DATA LOGGER RATE:
1 min
DATA LOGGER CHNL
MESSAGE
Off
DATA LOGGER CHNL
MESSAGE
Off
DATA LOGGER CHNL 16:
MESSAGE
Off
DATA LOGGER CONFIG:
MESSAGE
0 CHNL x
DEMAND
CRNT DEMAND METHOD:
Thermal Exponential
POWER DEMAND METHOD:
MESSAGE
Thermal Exponential
DEMAND INTERVAL:
MESSAGE
15 MIN
DEMAND TRIGGER:
MESSAGE
Off
T60 Transformer Management Relay
Range: 1 sec; 1 min, 5 min, 10 min, 15 min, 20 min, 30
min, 60 min
Range: Off, any FlexAnalog parameter. See Appendix A:
1:
FlexAnalog Parameters for complete list.
Range: Off, any FlexAnalog parameter. See Appendix A:
2:
FlexAnalog Parameters for complete list.
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
Range: Not applicable - shows computed data only
0.0 DAYS
Range: Thermal Exponential, Block Interval,
Rolling Demand
Range: Thermal Exponential, Block Interval,
Rolling Demand
Range: 5, 10, 15, 20, 30, 60 minutes
Range: FlexLogic™ operand
Note: for calculation using Method 2a
5 SETTINGS
5.2.9 DATA LOGGER
5.2.10 DEMAND