5 SETTINGS
The operands available for this relay are listed alphabetically by types in the following table.
Table 5–7: T60 FLEXLOGIC™ OPERANDS (Sheet 1 of 4)
OPERAND TYPE
OPERAND SYNTAX
CONTROL
CONTROL PUSHBTN n ON
PUSHBUTTONS
DIRECT DEVICES
DIRECT DEVICE 1 On
DIRECT DEVICE 16 On
DIRECT DEVICE 1 Off
DIRECT DEVICE 16 Off
DIRECT I/O
DIR IO CH1(2) CRC ALARM
CHANNEL
MONITORING
DIR IO CRC ALARM
DIR IO CH1(2) UNRET ALM
DIR IO UNRET ALM
ELEMENT:
AUX OV1 PKP
Auxiliary OV
AUX OV1 DPO
AUX OV1 OP
ELEMENT:
AUX UV1 PKP
Auxiliary UV
AUX UV1 DPO
AUX UV1 OP
ELEMENT:
Counter 1 HI
Digital Counter
Counter 1 EQL
Counter 1 LO
Counter 8 HI
Counter 8 EQL
Counter 8 LO
ELEMENT:
Dig Element 1 PKP
Digital Element
Dig Element 1 OP
Dig Element 1 DPO
Dig Element 16 PKP
Dig Element 16 OP
Dig Element 16 DPO
ELEMENT:
FxE 1 PKP
FlexElements™
FxE 1 OP
FxE 1 DPO
FxE 16 PKP
FxE 16 OP
FxE 16 DPO
ELEMENT:
GROUND IOC1 PKP
Ground IOC
GROUND IOC1 OP
GROUND IOC1 DPO
GROUND IOC2 to IOC8
ELEMENT:
GROUND TOC1 PKP
Ground TOC
GROUND TOC1 OP
GROUND TOC1 DPO
GROUND TOC2 to TOC6
ELEMENT
LATCH 1 ON
Non-Volatile
LATCH 1 OFF
Latches
LATCH 16 ON
LATCH 16 OFF
ELEMENT:
NEUTRAL IOC1 PKP
Neutral IOC
NEUTRAL IOC1 OP
NEUTRAL IOC1 DPO
NEUTRAL IOC2 to IOC8
ELEMENT:
NEUTRAL OV1 PKP
Neutral OV
NEUTRAL OV1 DPO
NEUTRAL OV1 OP
GE Multilin
OPERAND DESCRIPTION
Control Pushbutton n (n = 1 to 7) is being pressed.
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
The rate of Direct Input messages received on Channel 1(2) and failing the
CRC exceeded the user-specified level.
The rate of Direct Input messages failing the CRC exceeded the user-
specified level on Channel 1 or 2.
The rate of returned Direct I/O messages on Channel 1(2) exceeded the
user-specified level (ring configurations only).
The rate of returned Direct I/O messages exceeded the user-specified level
on Channel 1 or 2 (ring configurations only).
Auxiliary Overvoltage element has picked up
Auxiliary Overvoltage element has dropped out
Auxiliary Overvoltage element has operated
Auxiliary Undervoltage element has picked up
Auxiliary Undervoltage element has dropped out
Auxiliary Undervoltage element has operated
Digital Counter 1 output is 'more than' comparison value
Digital Counter 1 output is 'equal to' comparison value
Digital Counter 1 output is 'less than' comparison value
Digital Counter 8 output is 'more than' comparison value
Digital Counter 8 output is 'equal to' comparison value
Digital Counter 8 output is 'less than' comparison value
Digital Element 1 is picked up
Digital Element 1 is operated
Digital Element 1 is dropped out
Digital Element 16 is picked up
Digital Element 16 is operated
Digital Element 16 is dropped out
FlexElement™ 1 has picked up
FlexElement™ 1 has operated
FlexElement™ 1 has dropped out
FlexElement™ 16 has picked up
FlexElement™ 16 has operated
FlexElement™ 16 has dropped out
Ground Instantaneous Overcurrent 1 has picked up
Ground Instantaneous Overcurrent 1 has operated
Ground Instantaneous Overcurrent 1 has dropped out
Same set of operands as shown for GROUND IOC 1
Ground Time Overcurrent 1 has picked up
Ground Time Overcurrent 1 has operated
Ground Time Overcurrent 1 has dropped out
Same set of operands as shown for GROUND TOC1
Non-Volatile Latch 1 is ON (Logic = 1)
Non-Voltage Latch 1 is OFF (Logic = 0)
Non-Volatile Latch 16 is ON (Logic = 1)
Non-Voltage Latch 16 is OFF (Logic = 0)
Neutral Instantaneous Overcurrent 1 has picked up
Neutral Instantaneous Overcurrent 1 has operated
Neutral Instantaneous Overcurrent 1 has dropped out
Same set of operands as shown for NEUTRAL IOC1
Neutral Overvoltage element has picked up
Neutral Overvoltage element has dropped out
Neutral Overvoltage element has operated
T60 Transformer Management Relay
5.4 FLEXLOGIC™
5
5-59