3.3 DIRECT I/O COMMUNICATIONS
d) RECEIVE TIMING
The RS422 Interface utilizes NRZI-MARK Modulation Code and; therefore, does not rely on an Rx Clock to recapture data.
NRZI-MARK is an edge-type, invertible, self-clocking code.
To recover the Rx Clock from the data-stream, an integrated DPLL (Digital Phase Lock Loop) circuit is utilized. The DPLL is
driven by an internal clock, which is over-sampled 16X, and uses this clock along with the data-stream to generate a data
clock that can be used as the SCC (Serial Communication Controller) receive clock.
The following figure shows the combined RS422 plus Fiber interface configuration at 64K baud. The 7L, 7M, 7N, 7P, and 74
modules are used in 2-terminal with a redundant channel or 3-terminal configurations where Channel 1 is employed via the
RS422 interface (possibly with a multiplexer) and Channel 2 via direct fiber.
3
AWG 22 twisted shielded pair is recommended for external RS422 connections and the shield should be grounded only at
one end. For the direct fiber channel, power budget issues should be addressed properly.
When using a LASER Interface, attenuators may be necessary to ensure that you do not exceed Maximum
Optical Input Power to the receiver.
WARNING
Connections shown above are for multiplexers configured as DCE (Data Communications Equipment) units.
The figure below shows the combined G.703 plus Fiber interface configuration at 64K baud. The 7E, 7F, 7G, 7Q, and 75
modules are used in configurations where Channel 1 is employed via the G.703 interface (possibly with a multiplexer) and
Channel 2 via direct fiber. AWG 22 twisted shielded pair is recommended for external G.703 connections connecting the
shield to Pin 1A at one end only. For the direct fiber channel, power budget issues should be addressed properly. See pre-
vious sections for more details on the G.703 and Fiber interfaces.
When using a LASER Interface, attenuators may be necessary to ensure that you do not exceed Maximum
Optical Input Power to the receiver.
WARNING
3-28
3b
W
Tx1 -
W
3a
Rx1 -
W
2a
Tx1 +
W
4b
Rx1 +
W
6a
Shld.
Tx2
Rx2
W
7a
+
W
8b
-
W
2b
com
W
8a
Figure 3–33: RS422 AND FIBER INTERFACE CONNECTION
X
1a
Shld.
X
1b
Tx -
X
2a
Rx -
X
Tx +
2b
X
3a
Rx +
X
3b
Tx2
Rx2
Figure 3–34: G.703 AND FIBER INTERFACE CONNECTION
T60 Transformer Management Relay

3.3.6 RS422 AND FIBER INTERFACE

RS422
CHANNEL 1
FIBER
CHANNEL 2
CLOCK
(CHANNEL1)
SURGE
L907LMNP.CDR
P/O 827831A6.CDR
3.3.7 G.703 AND FIBER INTERFACE
G.703
CHANNEL 1
SURGE
FIBER
CHANNEL 2
3 HARDWARE