5.5 GROUPED ELEMENTS
f) AUXILIARY OVERVOLTAGE (ANSI 59X)
PATH: SETTINGS
GROUPED ELEMENTS
AUXILIARY OV1
This element is intended for monitoring overvoltage conditions of the auxiliary voltage. A typical application for this element
5
is monitoring the zero-sequence voltage (3V_0) supplied from an open-corner-delta VT connection. The nominal secondary
voltage of the auxiliary voltage channel entered under
is the p.u. base used when setting the pickup level.
X5 SECONDARY
SETTING
AUX OV1
FUNCTION:
Disabled=0
Enabled=1
SETTING
AUX OV1 BLOCK:
Off=0
SETTING
AUX OV1 SIGNAL
SOURCE:
AUXILIARY VOLT (Vx)
5-110
SETTING GROUP 1(6)
AUX OV1
FUNCTION: Disabled
AUX OV1 SIGNAL
MESSAGE
SOURCE: SRC 1
AUX OV1 PICKUP:
MESSAGE
0.300 pu
AUX OV1 PICKUP
MESSAGE
DELAY: 1.00 s
AUX OV1 RESET
MESSAGE
DELAY: 1.00 s
AUX OV1 BLOCK:
MESSAGE
Off
AUX OV1 TARGET:
MESSAGE
Self-reset
AUX OV1 EVENTS:
MESSAGE
Disabled
SETTING
AUX OV1 PICKUP:
AND
RUN
<
Vx Pickup
Figure 5–63: AUXILIARY OVERVOLTAGE SCHEME LOGIC
T60 Transformer Management Relay
VOLTAGE ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
SYSTEM SETUP
AC INPUTS
SETTING
AUX OV1 PICKUP
DELAY :
AUX OV1 RESET
DELAY :
t
PKP
t
RST
5 SETTINGS
AUXILIARY OV1
VOLTAGE BANK X5
AUXILIARY VT
FLEXLOGIC OPERANDS
AUX OV1 OP
AUX OV1 DPO
AUX OV1 PKP
827836A2.CDR