GE t60 Instruction Manual page 315

Ur series transformer management relay
Hide thumbs Also See for t60:
Table of Contents

Advertisement

APPENDIX B
F174
ENUMERATION: TRANSDUCER RTD INPUT TYPE
0 = 100 Ohm Platinum, 1 = 120 Ohm Nickel,
2 = 100 Ohm Nickel, 3 = 10 Ohm Copper
F175
ENUMERATION: PHASE LETTERS
0 = A, 1 = B, 2 = C
F177
ENUMERATION: COMMUNICATION PORT
0 = NONE, 1 = COM1-RS485, 2 = COM2-RS485,
3 = FRONT PANEL-RS232, 4 = NETWORK
F180
ENUMERATION: PHASE/GROUND
0 = PHASE, 1 = GROUND
F181
ENUMERATION: ODD/EVEN/NONE
0 = ODD, 1 = EVEN, 2 = NONE
F183
ENUMERATION: AC INPUT WAVEFORMS
bitmask
definition
0
Off
1
8 samples/cycle
2
16 samples/cycle
3
32 samples/cycle
4
64 samples/cycle
F185
ENUMERATION: PHASE A,B,C, GROUND SELECTOR
0 = A, 1 = B, 2 = C, 3 = G
F186
ENUMERATION: MEASUREMENT MODE
0 = Phase to Ground, 1 = Phase to Phase
F189
ENUMERATION: INRUSH INHIBIT MODE
0 = Per Phase, 1 = 2-out-of-3, 2 = Average
GE Multilin
F190
ENUMERATION: SIMULATED KEYPRESS
bitmsk keypress
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
F192
ENUMERATION: ETHERNET OPERATION MODE
0 = Half-Duplex, 1 = Full-Duplex
F194
ENUMERATION: DNP SCALE
A bitmask of 0 = 0.01, 1 = 0.1, 2 = 1, 3 = 10, 4 = 100, 5 = 1000,
6 = 10000, 7 = 100000, 8 = 0.001
F197
ENUMERATION: DNP BINARY INPUT POINT BLOCK
bitmask
0
1
2
3
4
5
6
7
8
9
10
11
T60 Transformer Management Relay
B.4 MEMORY MAPPING
bitmsk keypress
---
21
Escape
use between real keys
22
Enter
1
23
Reset
2
24
User 1
3
25
User 2
4
26
User 3
5
27
User-programmable key 1
6
28
User-programmable key 2
7
29
User-programmable key 3
8
30
User-programmable key 4
9
31
User-programmable key 5
0
32
User-programmable key 6
Decimal Pt
33
User-programmable key 7
Plus/Minus
34
User-programmable key 8
Value Up
35
User-programmable key 9
Value Down
36
User-programmable key 10
Message Up
37
User-programmable key 11
Message Down
38
User-programmable key 12
Message Left
39
User 4 (control pushbutton)
Message Right
40
User 5 (control pushbutton)
Menu
41
User 6 (control pushbutton)
Help
42
User 7 (control pushbutton)
Input Point Block
Not Used
Virtual Inputs 1 to 16
Virtual Inputs 17 to 32
Virtual Outputs 1 to 16
Virtual Outputs 17 to 32
Virtual Outputs 33 to 48
Virtual Outputs 49 to 64
Contact Inputs 1 to 16
Contact Inputs 17 to 32
Contact Inputs 33 to 48
Contact Inputs 49 to 64
Contact Inputs 65 to 80
B
B-49

Advertisement

Table of Contents
loading