GE t60 Instruction Manual page 280

Ur series transformer management relay
Hide thumbs Also See for t60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 7 of 34)
ADDR
REGISTER NAME
2822
Ib Harmonics - 2nd to 25th (24 items)
283A
Reserved (8 items)
2842
Ic THD
2843
Ic Harmonics - 2nd to 25th (24 items)
285B
Reserved (8 items)
B
2863
...Repeated for module number 2
28C6
...Repeated for module number 3
2929
...Repeated for module number 4
298C
...Repeated for module number 5
29EF
...Repeated for module number 6
Expanded FlexStates (Read Only)
2B00
FlexStates, one per register (256 items)
Expanded Digital I/O states (Read Only)
2D00
Contact Input States, one per register (96 items)
2D80
Contact Output States, one per register (64 items)
2E00
Virtual Output States, one per register (64 items)
Expanded Remote I/O Status (Read Only)
2F00
Remote Device States, one per register (16 items)
2F80
Remote Input States, one per register (32 items)
Oscillography Values (Read Only)
3000
Oscillography Number of Triggers
3001
Oscillography Available Records
3002
Oscillography Last Cleared Date
3004
Oscillography Number Of Cycles Per Record
Oscillography Commands (Read/Write Command)
3005
Oscillography Force Trigger
3011
Oscillography Clear Data
User Programmable Fault Report Commands (Read/Write Command)
3060
User Fault Report Clear
User Programmable Fault Report Actuals (Read Only)
3070
Newest Record Number
3071
Cleared Date
3073
Report Date (10 items)
User Programmable Fault Report (Read/Write Setting) (2 modules)
3090
Fault Report 1 Fault Trigger
3091
Fault Report 1 Function
3092
Fault Report 1 Prefault Trigger
3093
Fault Report 1 Analog Channel x (32 items)
30B3
Fault Report 1 Reserved (5 items)
30B8
...Repeated for module number 2
Modbus File Transfer (Read/Write)
3100
Name of file to read
Modbus File Transfer (Read Only)
3200
Character position of current block within file
3202
Size of currently-available data block
3203
Block of data from requested file (122 items)
Event Recorder (Read Only)
3400
Events Since Last Clear
3402
Number of Available Events
3404
Event Recorder Last Cleared Date
Event Recorder (Read/Write Command)
3406
Event Recorder Clear Command
DCMA Input Values (Read Only) (24 modules)
34C0
DCMA Inputs x Value
B-14
RANGE
0 to 99.9
0 to 0.1
0 to 99.9
0 to 99.9
0 to 0.1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 400000000
0 to 65535
0 to 1
0 to 1
0 to 1
0 to 65535
0 to 4294967295
0 to 4294967295
0 to 65535
0 to 1
0 to 65535
0 to 65536
---
---
0 to 4294967295
0 to 65535
0 to 65535
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
-9999.999 to 9999.999
T60 Transformer Management Relay
APPENDIX B
UNITS
STEP
FORMAT
---
0.1
F001
---
0.1
F001
---
0.1
F001
---
0.1
F001
---
0.1
F001
---
1
F108
---
1
F108
---
1
F108
---
1
F108
---
1
F155
---
1
F108
---
1
F001
---
1
F001
---
1
F050
---
1
F001
---
1
F126
---
1
F126
---
1
F126
---
1
F001
---
1
F050
---
1
F050
---
1
F300
---
1
F102
---
1
F300
---
1
F600
---
---
F001
---
---
F204
---
1
F003
---
1
F001
---
1
F001
---
1
F003
---
1
F003
---
1
F050
---
1
F126
---
0.001
F004
DEFAULT
0
0
0
0
0
0 (Off)
0 (Off)
0 (Off)
0 (Off)
0 (Offline)
0 (Off)
0
0
0
0
0 (No)
0 (No)
0 (No)
0
0
0
0
0 (Disabled)
0
0
0
(none)
0
0
0
0
0
0
0 (No)
0
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents