5.7 INPUTS / OUTPUTS
In the above architecture, Devices 1 and 3 do not communicate directly. Therefore, Device 2 must act as a 'bridge'. The fol-
lowing settings should be applied:
UR IED 1:
DIRECT OUT 2 OPERAND:
DIRECT INPUT 5 DEVICE ID:
DIRECT INPUT 5 BIT NUMBER:
DIRECT INPUT 6 DEVICE ID:
DIRECT INPUT 6 BIT NUMBER:
UR IED 3:
DIRECT OUT 2 OPERAND:
DIRECT INPUT 5 DEVICE ID:
DIRECT INPUT 5 BIT NUMBER:
DIRECT INPUT 6 DEVICE ID:
5
DIRECT INPUT 6 BIT NUMBER:
UR IED 2:
DIRECT INPUT 5 DEVICE ID:
DIRECT INPUT 5 BIT NUMBER:
DIRECT INPUT 6 DEVICE ID:
DIRECT INPUT 6 BIT NUMBER:
DIRECT OUT 2 OPERAND:
DIRECT OUT 3 OPERAND:
DIRECT OUT 4 OPERAND:
Signal flow between the three IEDs is shown in the figure below:
UR IED 1
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, Direct
Inputs 5 and 6 should be ANDed in FlexLogic™ and the resulting operand configured as the permission to trip (
setting).
RX1
5-138
TX1
UR IED 1
RX1
UR IED 3
Figure 5–80: SINGLE-CHANNEL OPEN-LOOP CONFIGURATION
"
HYB POTT TX1
"2"
"2" (this is a message from IED 2)
"2"
"4" (effectively, this is a message from IED 3)
"
HYB POTT TX1
"2"
"2" (this is a message from IED 2)
"2"
"3" (effectively, this is a message from IED 1)
"1"
"2"
"3"
"2"
"
HYB POTT TX1
"
DIRECT INPUT 5
"
DIRECT INPUT 6
DIRECT OUT 2 = HYB POTT TX1
DIRECT INPUT 5
DIRECT INPUT 6
Figure 5–81: SIGNAL FLOW FOR DIRECT I/O EXAMPLE 3
T60 Transformer Management Relay
RX1
UR IED 2
TX1
RX1
TX1
"
"
"
" (forward a message from 1 to 3)
" (forward a message from 3 to 1)
UR IED 2
DIRECT INPUT 5
DIRECT OUT 2 = HYB POTT TX1
DIRECT OUT 4 = DIRECT INPUT 6
DIRECT OUT 3 = DIRECT INPUT 5
DIRECT INPUT 6
UR IED 3
DIRECT OUT 2 = HYB POTT TX1
5 SETTINGS
RX2
TX2
842714A1.CDR
DIRECT INPUT 5
DIRECT INPUT 6
842717A1.CDR
HYB POTT
GE Multilin