5.6 CONTROL ELEMENTS
APPLICATION EXAMPLE
Consider an application where the selector switch is used to control Setting Groups 1 through 4 in the relay. The setting
groups are to be controlled from both User-Programmable Pushbutton 1 and from an external device via Contact Inputs 1
through 3. The active setting group shall be available as an encoded 3-bit word to the external device and SCADA via out-
put contacts 1 through 3. The pre-selected setting group shall be applied automatically after 5 seconds of inactivity of the
control inputs. When the relay powers up, it should synchronize the setting group to the 3-bit control input.
Make the following changes to Setting Group Control in the
SETTING GROUPS FUNCTION:
SETTING GROUPS BLK:
GROUP 2 ACTIVATE ON:
GROUP 3 ACTIVATE ON:
Make the following changes to Selector Switch element in the
menu to assign control to User Programmable Pushbutton 1 and Contact Inputs 1 through 3:
SELECTOR SWITCH 1
SELECTOR 1 FUNCTION:
SELECTOR 1 FULL-RANGE:
SELECTOR 1 STEP-UP MODE:
SELECTOR 1 TIME-OUT:
SELECTOR 1 STEP-UP:
SELECTOR 1 ACK:
Now, assign the contact output operation (assume the H6E module) to the Selector Switch element by making the following
changes in the
SETTINGS
OUTPUT H1 OPERATE:
5
OUTPUT H2 OPERATE:
OUTPUT H3 OPERATE:
Finally, assign configure User-Programmable Pushbutton 1 by making the following changes in the
SETUP
USER-PROGRAMMABLE PUSHBUTTONS
PUSHBUTTON 1 FUNCTION:
PUSHBUTTON 1 DROP-OUT TIME:
The logic for the selector switch is shown below:
SELECTOR 1 FUNCTION:
Enabled = 1
SELECTOR 1 STEP-UP:
Off
SELECTOR 1 ACK:
Off
SELECTOR 1 3BIT A0:
Off
SELECTOR 1 3BIT A1:
Off
SELECTOR 1 3BIT A2:
Off
SELECTOR 1 3BIT ACK:
Off
5-118
"Enabled"
"Off"
"SELECTOR 1 POS 2"
"SELECTOR 1 POS 3"
"Enabled"
"4"
"Time-out"
"5.0 s"
"PUSHBUTTON 1 ON"
"Off"
INPUTS/OUTPUTS
CONTACT OUTPUTS
"SELECTOR 1 BIT 0"
"SELECTOR 1 BIT 1"
"SELECTOR 1 BIT 2"
"Self-reset"
"0.10 s"
SELECTOR 1 FULL RANGE:
SELECTOR 1 STEP-UP MODE:
SELECTOR 1 3BIT MODE:
SELECTOR 1 TIME-OUT:
SETTINGS
SELECTOR 1 POWER-UP MODE:
RUN
step up
acknowledge
3-bit
acknowledge
Figure 5–68: SELECTOR SWITCH LOGIC
T60 Transformer Management Relay
SETTINGS
CONTROL ELEMENTS
GROUP 4 ACTIVATE ON:
GROUP 5 ACTIVATE ON:
GROUP 6 ACTIVATE ON:
SETTINGS
CONTROL ELEMENTS
SELECTOR 1 3BIT A0:
SELECTOR 1 3BIT A1:
SELECTOR 1 3BIT A2:
SELECTOR 1 3BIT MODE:
SELECTOR 1 3BIT ACK:
SELECTOR 1 POWER-UP MODE:
menu:
menu:
USER PUSHBUTTON 1
SETTINGS
2
1
3
4
on
7
5
6
3-bit position out
5 SETTINGS
SETTING GROUPS
"SELECTOR 1 POS 4"
"Off"
"Off"
SELECTOR SWITCH
"CONT IP 1 ON"
"CONT IP 2 ON"
"CONT IP 3 ON"
"Time-out"
"Off"
"Synchronize"
SETTINGS
ACTUAL VALUE
SELECTOR 1 POSITION
FLEXLOGIC OPERANDS
SELECTOR 1 POS 1
SELECTOR 1 POS 2
SELECTOR 1 POS 3
SELECTOR 1 POS 4
SELECTOR 1 POS 5
SELECTOR 1 POS 6
SELECTOR 1 POS 7
FLEXLOGIC OPERANDS
SELECTOR 1 STP ALARM
SELECTOR 1 BIT ALARM
SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
842012A1.CDR