APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 24 of 34)
ADDR
REGISTER NAME
B016
Digital Element 1 Pickup Delay
B018
Digital Element 1 Reset Delay
B01A
Digital Element 1 Block
B01B
Digital Element 1 Target
B01C
Digital Element 1 Events
B01D
Digital Element 1 Reserved (3 items)
B020
...Repeated for module number 2
B040
...Repeated for module number 3
B060
...Repeated for module number 4
B080
...Repeated for module number 5
B0A0
...Repeated for module number 6
B0C0
...Repeated for module number 7
B0E0
...Repeated for module number 8
B100
...Repeated for module number 9
B120
...Repeated for module number 10
B140
...Repeated for module number 11
B160
...Repeated for module number 12
B180
...Repeated for module number 13
B1A0
...Repeated for module number 14
B1C0
...Repeated for module number 15
B1E0
...Repeated for module number 16
Digital Counter (Read/Write Setting) (8 modules)
B300
Digital Counter 1 Function
B301
Digital Counter 1 Name
B307
Digital Counter 1 Units
B30A
Digital Counter 1 Block
B30B
Digital Counter 1 Up
B30C
Digital Counter 1 Down
B30D
Digital Counter 1 Preset
B30F
Digital Counter 1 Compare
B311
Digital Counter 1 Reset
B312
Digital Counter 1 Freeze/Reset
B313
Digital Counter 1 Freeze/Count
B314
Digital Counter 1 Set To Preset
B315
Digital Counter 1 Reserved (11 items)
B320
...Repeated for module number 2
B340
...Repeated for module number 3
B360
...Repeated for module number 4
B380
...Repeated for module number 5
B3A0
...Repeated for module number 6
B3C0
...Repeated for module number 7
B3E0
...Repeated for module number 8
Contact Inputs (Read/Write Setting) (96 modules)
C000
Contact Input x Name
C006
Contact Input x Events
C007
Contact Input x Debounce Time
C008
...Repeated for module number 2
C010
...Repeated for module number 3
C018
...Repeated for module number 4
C020
...Repeated for module number 5
C028
...Repeated for module number 6
C030
...Repeated for module number 7
C038
...Repeated for module number 8
GE Multilin
RANGE
0 to 999999.999
0 to 999999.999
0 to 65535
0 to 2
0 to 1
---
0 to 1
---
---
0 to 65535
0 to 65535
0 to 65535
-2147483647 to
2147483647
-2147483647 to
2147483647
0 to 65535
0 to 65535
0 to 65535
0 to 65535
---
---
0 to 1
0 to 16
T60 Transformer Management Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
s
0.001
F003
s
0.001
F003
---
1
F300
---
1
F109
---
1
F102
---
---
F001
---
1
F102
---
---
F205
---
---
F206
---
1
F300
---
1
F300
---
1
F300
---
1
F004
---
1
F004
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
---
F001
---
---
F205
---
1
F102
ms
0.5
F001
DEFAULT
0
0
0
0 (Self-reset)
0 (Disabled)
B
0
0 (Disabled)
"Counter 1 "
(none)
0
0
0
0
0
0
0
0
0
0
"Cont Ip 1 "
0 (Disabled)
20
B-31