Remote Outputs - GE t60 Instruction Manual

Ur series transformer management relay
Hide thumbs Also See for t60:
Table of Contents

Advertisement

5.7 INPUTS / OUTPUTS
a) DNA BIT PAIRS
PATH: SETTINGS
INPUTS/OUTPUTS

REMOTE OUTPUTS

DNA- 1 BIT PAIR
Remote Outputs (1 to 32) are FlexLogic™ operands inserted into GOOSE messages that are transmitted to remote
devices on a LAN. Each digital point in the message must be programmed to carry the state of a specific FlexLogic™ oper-
and. The above operand setting represents a specific DNA function (as shown in the following table) to be transmitted.
Table 5–22: UCA DNA2 ASSIGNMENTS
DNA
DEFINITION
1
OperDev
2
Lock Out
3
Initiate Reclosing
4
Block Reclosing
5
Breaker Failure Initiate
6
Send Transfer Trip
7
Receive Transfer Trip
5
8
Send Perm
9
Receive Perm
10
Stop Perm
11
Send Block
12
Receive Block
13
Stop Block
14
BkrDS
15
BkrPhsADS
16
BkrPhsBDS
17
BkrPhsCDS
18
DiscSwDS
19
Interlock DS
20
LineEndOpen
21
Status
22
Event
23
Fault Present
24
Sustained Arc
25
Downed Conductor
26
Sync Closing
27
Mode
28→32
Reserved
For more information on GOOSE specifications, see the Remote I/O Overview in the Remote Devices sec-
tion.
NOTE
5-134
REMOTE OUTPUTS DNA BIT PAIRS
DNA- 1 OPERAND:
Off
DNA- 1 EVENTS:
MESSAGE
Disabled
INTENDED FUNCTION
Initiate remote reclose sequence
Prevent/cancel remote reclose sequence
Initiate remote breaker failure scheme
Initiate remote trip operation
Report receipt of remote transfer trip command
Report permissive affirmative
Report receipt of permissive affirmative
Override permissive affirmative
Report block affirmative
Report receipt of block affirmative
Override block affirmative
Report breaker disconnect 3-phase state
Report breaker disconnect phase A state
Report breaker disconnect phase B state
Report breaker disconnect phase C state
Report line open at local end
Report operating status of local GOOSE device
Report sustained arc
Report downed conductor
Report mode status of local GOOSE device
T60 Transformer Management Relay
5.7.8 REMOTE OUTPUTS
REMOTE OUPUTS DNA- 1(32) BIT PAIR
Range: FlexLogic™ Operand
Range: Disabled, Enabled
LOGIC 0
Trip
LockoutOff
InitRecloseOff
BlockOff
BFIOff
TxXfrTripOff
RxXfrTripOff
TxPermOff
RxPermOff
StopPermOff
TxBlockOff
RxBlockOff
StopBlockOff
Open
Open
Open
Open
Open
DSLockOff
Open
Offline
EventOff
FaultOff
SustArcOff
DownedOff
SyncClsOff
Normal
5 SETTINGS
LOGIC 1
Close
LockoutOn
InitRecloseOn
BlockOn
BFIOn
TxXfrTripOn
RxXfrTripOn
TxPermOn
RxPermOn
StopPermOn
TxBlockOn
RxBlockOn
StopBlockOn
Closed
Closed
Closed
Closed
Closed
DSLockOn
Closed
Available
EventOn
FaultOn
SustArcOn
DownedOn
SyncClsOn
Test
GE Multilin

Advertisement

Table of Contents
loading