Setting Guideline - ABB RELION 670 SERIES REG670 Applications Manual

Generator protection
Hide thumbs Also See for RELION 670 SERIES REG670:
Table of Contents

Advertisement

Section 9
Current protection
9.7.3
396
The protection can have two sets of parameters, one for non-forced cooling and one for
forced cooling. Both the permissive steady state loading level as well as the thermal
time constant is influenced by the cooling system of the transformer. The two
parameters sets can be activated by the binary input signal COOLING. This can be
used for transformers where forced cooling can be taken out of operation, for example
at fan or pump faults.
The thermal overload protection estimates the internal heat content of the transformer
(temperature) continuously. This estimation is made by using a thermal model of the
transformer which is based on current measurement.
If the heat content of the protected transformer reaches a set alarm level a signal can be
given to the operator. Two alarm levels are available. This enables preventive actions
in the power system to be taken before dangerous temperatures are reached. If the
temperature continues to increase to the trip value, the protection initiates a trip of the
protected transformer.
After tripping by the thermal overload protection, the transformer will cool down over
time. There will be a time gap before the heat content (temperature) reaches such a
level so that the transformer can be taken into service again. Therefore, the function
will continue to estimate the heat content using a set cooling time constant. Energizing
of the transformer can be blocked until the heat content has reached a set level.

Setting guideline

The parameters for the thermal overload protection, two time constants (TRPTTR, 49)
are set via the local HMI or Protection and Control IED Manager (PCM600).
The following settings can be done for the thermal overload protection:
Operation: Disabled/Enabled
Operation: Sets the mode of operation. Disabled switches off the complete function.
GlobalBaseSel: Selects the global base value group used by the function to define
(IBase), (UBase) and (SBase).
IRef: Reference level of the current given in % of IBase. When the current is equal to
IRef the final (steady state) heat content is equal to 1. It is suggested to give a setting
corresponding to the rated current of the transformer winding.
IRefMult: If a binary input ENMULT is activated the reference current value can be
multiplied by the factor IRefMult. The activation could be used in case of deviating
ambient temperature from the reference value. In the standard for loading of a
transformer an ambient temperature of 20°C is used. For lower ambient temperatures
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
1MRK 502 071-UUS A
M13250-3 v8
Application manual

Advertisement

Table of Contents
loading

Table of Contents