ABB RELION 670 SERIES REG670 Applications Manual page 393

Generator protection
Hide thumbs Also See for RELION 670 SERIES REG670:
Table of Contents

Advertisement

1MRK 502 071-UUS A
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual
Where
I
is the capacitive ground fault current at a non-resistive phase-to-ground fault
j
X
is the capacitive reactance to ground
c
In a system with a neutral point resistor (resistance grounded system) the impedance Z
can be calculated as:
-
×
jX 3R
=
Z
c
n
0
-
+
jX
3R
c
n
EQUATION1946 V1 EN-US
Where
R
is the resistance of the neutral point resistor
n
In many systems there is also a neutral point reactor (Petersen coil) connected to one or
more transformer neutral points. In such a system the impedance Z
as:
= -
=
Z
jX // 3R // j3X
0
c
n
n
EQUATION1947 V1 EN-US
Where
X
is the reactance of the Petersen coil. If the Petersen coil is well tuned we have 3X
n
case the impedance Z
Now consider a system with an grounding via a resistor giving higher ground fault
current than the high impedance grounding. The series impedances in the system can
no longer be neglected. The system with a single phase to ground fault can be
described as in Figure 190.
9R X X
n
n
c
(
+
×
-
3X X
j3R
3X
X
n
c
n
n
c
will be: Z
= 3R
0
0
n
Section 9
Current protection
can be calculated
0
)
n
0
(Equation 191)
(Equation 192)
= X
In this
c
387

Advertisement

Table of Contents
loading

Table of Contents