Setting Guidelines - ABB RELION 670 SERIES REG670 Applications Manual

Generator protection
Hide thumbs Also See for RELION 670 SERIES REG670:
Table of Contents

Advertisement

Section 9
Current protection
9.6.3
386

Setting guidelines

The sensitive ground-fault protection is intended to be used in high impedance
grounded systems, or in systems with resistive grounding where the neutral point
resistor gives an ground-fault current larger than what normal high impedance gives
but smaller than the phase to phase short circuit current.
In a high impedance system the fault current is assumed to be limited by the system
zero sequence shunt impedance to ground and the fault resistance only. All the series
impedances in the system are assumed to be zero.
In the setting of ground-fault protection, in a high impedance grounded system, the
neutral point voltage (zero sequence voltage) and the ground-fault current will be
calculated at the desired sensitivity (fault resistance). The complex neutral point
voltage (zero sequence) can be calculated as:
V
=
phase
V
×
0
3 R
+
1
f
Z
0
EQUATION2020-ANSI V1 EN-US
Where
V
is the phase voltage in the fault point before the fault,
phase
R
is the resistance to ground in the fault point and
f
Z
is the system zero sequence impedance to ground
0
The fault current, in the fault point, can be calculated as:
×
3 V
phase
=
=
I
3I
j
0
+ ×
Z
3 R
0
f
EQUATION2021 V1 EN-US
The impedance Z
is dependent on the system grounding. In an isolated system
0
(without neutral point apparatus) the impedance is equal to the capacitive coupling
between the phase conductors and ground:
×
3 V
= -
= -
phase
Z
jX
j
0
c
I
j
EQUATION2022-ANSI V1 EN-US
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
1MRK 502 071-UUS A
SEMOD171961-4 v10
(Equation 188)
(Equation 189)
(Equation 190)
Application manual

Advertisement

Table of Contents
loading

Table of Contents