Section 17
Monitoring
714
140°C
130°C
120°C
110°C
100°C
90°C
80°C
10
12
2
4
6
8
12
Hours of the day
Normal life expectancy loading
140°C
130°C
120°C
110°C
100°C
90°C
80°C
10
12
2
4
6
8
12
Hours of the day
Long time energy loading
IEC15000441 V1 EN-US
Figure 316:
Typical load cycles for example
Impact of the increased currents and temperature leads to premature transformer failure
and this may have an immediate short term effect or a cumulative long term effect.
Short-term effect: Reduction in dielectric strength due to the possible presence of
gas bubbles which leads to super saturation of the oil and reduction in short circuit
strength.
Long-term effect: Continuous deterioration of the conductor reduces the
transformer life.
Deterioration of insulation reduces mechanical strength and dielectric strength. Heating
from heavy overload or large electromagnetic force resulting from short circuit causes
expansion and unusual movement of conductors and it leads to turn-to-turn fault.
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
140°C
130°C
120°C
110°C
100°C
90°C
80°C
2
4
6
8
10
12
2
170°C
160°C
150°C
140°C
130°C
120°C
110°C
100°C
90°C
2
4
6
8
10
12
2
1MRK 502 071-UUS A
10
4
6
8
12
2
4
6
Hours of the day
Planned loading beyond nameplate rating
10
4
6
8
12
2
4
6
Hours of the day
Short time energy loading
IEC15000441-1-en.vsdx
Application manual
8
10
8
10