Example 3 - ABB RELION 670 SERIES REG670 Applications Manual

Generator protection
Hide thumbs Also See for RELION 670 SERIES REG670:
Table of Contents

Advertisement

Section 4
Analog inputs
4.2.2.3
70

Example 3

One IED used to protect two objects.
Transformer
Setting of current input:
Set parameter
CT_WyePoint with
Transformer as
reference object.
Correct setting is
"ToObject"
ANSI05000461 V1 EN-US
Figure 14:
Example how to set CT_WyePoint parameters in the IED
In this example, one IED includes both transformer and line protections and the line
protection uses the same CT as the transformer protection does. For both current input
channels, the CT direction is set with the transformer as reference object. This means
that the direction Forward for the line protection is towards the transformer. To look
towards the line, the direction of the directional functions of the line protection must be
set to Reverse. The direction Forward/Reverse is related to the reference object that is
the transformer in this case.
When a function is set to Reverse and shall protect an object in reverse direction, it
shall be noted that some directional functions are not symmetrical regarding the reach
in forward and reverse direction. It is in first hand the reach of the directional criteria
that can differ. Normally it is not any limitation but it is advisable to have it in mind
and check if it is acceptable for the application in question.
If the IED has sufficient number of analog current inputs, an alternative solution is
shown in Figure 15. The same currents are fed to two separate groups of inputs and the
line and transformer protection functions are configured to the different inputs. The CT
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Transformer and
Line protection
Setting of current input:
Set parameter
CT_WyePoint with
Transformer as
reference object.
Correct setting is
"ToObject"
1MRK 502 071-UUS A
SEMOD55055-35 v7
Line
Forward
Reverse
Definition of direction for
directional
line functions
en05000461_ansi.vsd
Application manual

Advertisement

Table of Contents
loading

Table of Contents