Section 8
Impedance protection
226
TimerModeZx =
Enable Ph-Ph,
Ph-G
PPZx
AND
PGZx
AND
BLOCK
LOVBZ
BLKZx
OR
BLKTRZx
ZoneLinkStart
PUPHS
Phase Selection
1st pickup zone
LNKZ1
LNKZ2
LNKZRV
LNKZ3
OR
LNKZ4
LNKZ5
ANSI12000139 V2 EN-US
Figure 94:
Logic for linking of timers
CVTtype
If possible, the type of capacitive voltage transformer (CVT) used for measurement
should be identified. The alternatives are strongly related to the type of ferro-resonance
suppression circuit included in the CVT. There are two main choices:
Passive type
For CVTs that use a nonlinear component, like a saturable inductor, to limit overvoltages
(caused by ferro-resonance). This component is practically idle during normal load and
fault conditions, hence the name "passive." CVTs that have a high resistive burden to
mitigate ferro-resonance also fall into this category.
Any
This option is primarily related to the so-called active type CVT, which uses a set of
reactive components to form a filter circuit that essentially attenuates frequencies other
than the nominal to restrain the ferro-resonance. The name "active" refers to this circuit
always being involved during transient conditions, regardless of the voltage level. This
option should also be used for the types that do not fall under the other two categories, for
example, CVTs with power electronic damping devices, or if the type cannot be identified
at all.
None
This option should be selected if the voltage transformer is fully magnetic.
(Magnetic)
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
OR
AND
tPPZx
AND
0
OR
tPPZx
AND
AND
0
TimerLinksZx
OR
LoopLink (tPP-tPG)
LoopLink & ZoneLink
OR
no links
FALSE (0)
TimerLinksZx =
LoopLink & ZoneLink
1MRK 502 071-UUS A
TZx
OR
LNKZx
AND
ANSI12000139-2-en.vsdx
Application manual