Section 3 Configuration; Description Of Reg670; Introduction; Description Of Configuration A20 - ABB RELION 670 SERIES REG670 Applications Manual

Generator protection
Hide thumbs Also See for RELION 670 SERIES REG670:
Table of Contents

Advertisement

1MRK 502 071-UUS A
Section 3
3.1
3.1.1
3.1.1.1
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual
Configuration

Description of REG670

Introduction

Description of configuration A20

REG670 A20 configuration is used in applications where only generator protection
within one IED is required. REG670 A20 is always delivered in 1/2 of 19" case size.
Thus only 12 analogue inputs are available. This configuration includes generator low
impedance, differential protection and all other typically required generator protection
functions. Note that 100% stator earth fault function and Pole Slip protection function
are optional.
REG670 A20 functional library includes additional functions, which are not
configured, such as additional Overcurrent protection, additional Multipurpose
protection functions, Synchronizing function, and so on. It is as well possible to order
optional two-winding transformer differential or high impedance differential protection
functions which than can be used instead of basic low-impedance generator differential
protection. Note that REG670 A20 must be re-configured if any additional or optional
functions are used.
Section 3
Configuration
SEMOD175634-1 v2
SEMOD175645-1 v1
SEMOD175637-4 v5
61

Advertisement

Table of Contents
loading

Table of Contents