ABB RELION 670 SERIES REG670 Applications Manual page 81

Generator protection
Hide thumbs Also See for RELION 670 SERIES REG670:
Table of Contents

Advertisement

1MRK 502 071-UUS A
A
CT 600/5
Wye Connected
Protected Object
ANSI13000002 V3 EN-US
Figure 18:
Wye connected three-phase CT set with wye point towards the protected object
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual
B
C
I_A
I_B
I_C
Where:
1)
The drawing shows how to connect three individual phase currents from a wye connected
three-phase CT set to the three CT inputs of the IED.
2)
The current inputs are located in the TRM. It shall be noted that for all these current inputs the
following setting values shall be entered for the example shown in Figure 18.
CTprim=600A
CTsec=5A
CTStarPoint=ToObject
Ratio of the first two parameters is only used inside the IED. The third parameter
(CTStarPoint=ToObject) as set in this example causes no change on the measured currents. In
other words, currents are already measured towards the protected object.
Table continues on next page
IED
1
2
3
Section 4
Analog inputs
4
SMAI_20
ANSI13000002-3-en.vsd