Section 9
Current protection
376
Single phase-
to- ground fault
ANSI05000493 V3 EN-US
Figure 186:
Step 1 fault calculation 1
The fault is located at the borderline between instantaneous and delayed operation of
the line protection, such as Distance protection or line residual overcurrent protection.
This calculation gives the current fed to the protection: 3I
The setting of step 1 can be chosen within the interval shown in equation 186.
×
<
3I
lowmar
I
0fault 2
step1
EQUATION1455 V2 EN-US
Where:
lowmar
is a margin to assure selectivity (typical 1.2) and
highmar is a margin to assure fast fault clearance of busbar fault (typical 1.2).
Setting of step 2
The setting of the sensitive step 2 is dependent of the chosen time delay. Often a
relatively long definite time delay or inverse time delay is chosen. The current setting
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Three phase CT
summated
3I
0
alt
67N
<
×
3I
highmar
0fault1
1MRK 502 071-UUS A
YN/D or YN/Y
transformer
Single CT
ANSI05000493_3_en.vsd
0fault2
(Equation 186)
Application manual
SEMOD55591-57 v5