ABB RELION 670 SERIES REG670 Applications Manual page 489

Generator protection
Hide thumbs Also See for RELION 670 SERIES REG670:
Table of Contents

Advertisement

1MRK 502 071-UUS A
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual
The user can select, by a setting parameter CurrentInput, to measure one of the
following current quantities shown in table 48.
Table 48:
Available selection for current quantity within CVGAPC function
Set value for parameter
"CurrentInput"
PhaseA
1
PhaseB
2
3
PhaseC
PosSeq
4
NegSeq
5
6
3 · ZeroSeq
MaxPh
7
MinPh
8
UnbalancePh
9
PhaseA - PhaseB
10
PhaseB - PhaseC
11
PhaseC - PhaseA
12
MaxPh-Ph
13
MinPh-Ph
14
UnbalancePh-Ph
15
The user can select, by a setting parameter VoltageInput, to measure one of the
following voltage quantities shown in table 49.
Multipurpose protection
Comment
CVGAPC function will measure the phase A current phasor
CVGAPC function will measure the phase B current phasor
CVGAPC function will measure the phase C current phasor
CVGAPC function will measure internally calculated positive
sequence current phasor
CVGAPC function will measure internally calculated negative
sequence current phasor
CVGAPC function will measure internally calculated zero sequence
current phasor multiplied by factor 3
CVGAPC function will measure current phasor of the phase with
maximum magnitude
CVGAPC function will measure current phasor of the phase with
minimum magnitude
CVGAPC function will measure magnitude of unbalance current,
which is internally calculated as the algebraic magnitude difference
between the current phasor of the phase with maximum magnitude
and current phasor of the phase with minimum magnitude. Phase
angle will be set to 0° all the time
CVGAPC function will measure the current phasor internally
calculated as the vector difference between the phase A current
phasor and phase B current phasor (VA-VB)
CVGAPC function will measure the current phasor internally
calculated as the vector difference between the phase B current
phasor and phase C current phasor (VB-VC)
CVGAPC function will measure the current phasor internally
calculated as the vector difference between the phase C current
phasor and phase A current phasor ( VC-VA)
CVGAPC function will measure ph-ph current phasor with the
maximum magnitude
CVGAPC function will measure ph-ph current phasor with the
minimum magnitude
CVGAPC function will measure magnitude of unbalance current,
which is internally calculated as the algebraic magnitude difference
between the ph-ph current phasor with maximum magnitude and
ph-ph current phasor with minimum magnitude. Phase angle will be
set to 0° all the time