Application - ABB RELION 670 SERIES REG670 Applications Manual

Generator protection
Hide thumbs Also See for RELION 670 SERIES REG670:
Table of Contents

Advertisement

1MRK 502 071-UUS A
8.4.2
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual

Application

Normally, the generator operates synchronously with the power system, that is, all the
generators in the system have the same angular velocity and approximately the same
phase angle difference. If the phase angle between the generators gets too large the
stable operation of the system cannot be maintained. In such a case the generator loses
the synchronism (pole slip) to the external power system.
The situation with pole slip of a generator can be caused by different reasons.
A short circuit occurs in the external power grid, close to the generator. If the fault
clearance time is too long, the generator will accelerate so much, so the synchronism
cannot be maintained. The relative generator phase angle at a fault and pole slip,
relative to the external power system, is shown in figure 134.
IEC06000313 V1 EN-US
Figure 134:
Relative generator phase angle at a fault and pole slip relative to the
external power system
The relative angle of the generator is shown for different fault duration at a three-phase
short circuit close to the generator. As the fault duration increases the angle swing
Section 8
Impedance protection
SEMOD143248-4 v3
en06000313.vsd
281