9.
Set BG Threshold – Allows the user to alter the Background threshold that will prompt a
Background fault when the set level is met. Note; this would normally be set 20dB Higher
than the background (background found within the node status menu). For example, with
a background level found to be at a level of -110, we would set the BG Threshold to -90.
10. Set CS Threshold – Allows the user to alter the Carrier Sensor threshold that when the
ambient background level is met will hold off transmissions until the air has cleared. Note;
this would normally be set 3dB Higher than the BG Threshold and 23dB higher than the
background. For example, with a background level found to be at a level of -110, and the
BG Threshold is set to -90, we would set the CS threshold to -87dB.
Note: The Site ID 1, Poll Rate, Poll Timeout and Baud Rate must be programmed the same on all
Radio Network Communicators (Nodes) across the Network.