Download Print this page
EMS FireCell FC-555-001 Installation Manual

EMS FireCell FC-555-001 Installation Manual

230 vac radio cluster communicator

Advertisement

Quick Links

230 VAC Radio Cluster Communicator (RCC)
Installation Guide
POWER
FAULT
1 Pre installation
Installation must conform to applicable local installation
!
codes and should only be installed by a fully trained
competent person.
Ensure the RCC is installed as per the site survey.
Refer to step 3 to ensure optimised wireless performance.
If using remote aerials with this product, refer to the remote
aerial installation guide for more information.
This device contains electronics that may be susceptible to
damage from Electrostatic Discharge (ESD). Take appropriate
precautions when handling electronic boards.
3 Mounting location guidelines
For optimum wireless
p e r f o r m a n c e , t h e
following
must
observed:
Ensure the RCC is not installed
within 2 m of other wireless or
electrical equipment.
The RCC must not be installed
within 0.6 m of any metal
work.
5 Remove cable entry points
Drill the cable entry
points as necessary.
= DO NOT use
= Available cable
entry points
©2021 EMS Ltd. All rights reserved
RADIO CLUSTER COMMUNICATOR
2 m
be
0.6 m
RCC
POWER
FAULT
Part no
Product description
FC-555-001
230 VAC RCC c/w PSU
FC-555-331
230 VAC RCC c/w remote aerial facility & PSU
2 Components
1
2
3
1
4x corner covers
4
1x RCC PCB
4 Optional PCB / PSU removal
Remove the three circled retaining screws, prior to unclipping
the PCB.
If removing or rotating the PSU for right hand side mains
entry, remove both PSU retaining screws.
RF1
RF2
RESET
HEALTHY
FAULT
SYS FAULT
For additional information refer to TSD042
6 Fix to the wall
All
five
circled
fixing
positions
are available for
use.
The key hole can
also be used for
locating
and
fixing
where
required.
Page 1 of 2
4
2
4x lid screws
3
5
6
1x RCC PSU
1x RCC back box
RF1
RESET
HEALTHY
FAULT
SYS FAULT
For additional information refer to TSD042
BACK
LOGON
TSD053-99 Iss 26 15/12/2021 AJM
5
6
1x RCC lid
RF2
BACK
LOGON

Advertisement

loading

Summary of Contents for EMS FireCell FC-555-001

  • Page 1 The key hole can also be used for locating fixing where required. = DO NOT use = Available cable entry points ©2021 EMS Ltd. All rights reserved Page 1 of 2 TSD053-99 Iss 26 15/12/2021 AJM...
  • Page 2 *Typical 5 year battery life based on normal usage. Note; if 72 hours battery standby is required, it is recommended that the European Union EMS declares that this device is in compliance with battery is replaced every 3 years. directives Directive 2014/53/EU.

This manual is also suitable for: