EMS FireCell FCX-438-001 Installation Manual

Radio network communicator (rnc)

Advertisement

Quick Links

Radio Network Communicator (RNC)
Installation Guide
1 Pre Installation
Installation must conform to applicable local installation
!
codes and should only be installed by a fully trained
competent person.
Ensure the RNC is installed as per the site survey.
Refer to step 3 to ensure optimised wireless performance.
If using remote aerials with this product, refer to the Remote
Network Communicator Installation details document (TSD105)
for more information.
3 Mounting Location Guidelines
For optimum wireless
p e r f o r m a n c e , t h e
following
must
observed:
Ensure the RNC is not installed
within 2m of other wireless or
electrical equipment (including
the Control Panel)
The RNC's aerial must not be
installed within 0.6m of any
metal work.
RNCs connected to Syncro AS
panels must also have a high
gain aerial fitted, with the aerial
and RNC separated by 5m.
5 Remove Cable Entry Points
Drill the cable entry points as
necessary.
= Do Not Use
= Available Cable
Entry Points
©2018 EMS Ltd. All rights reserved
Radio Network Communicator
POWER
FAULT
NETWORK FAULT
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE
2m
be
0.6m
RNC
Radio Network Communicator
POWER
FAULT
NETWORK FAULT
FIRE
Fire
Panel
Fire Alarm Control
Part No
FCX-438-001
2 Components
1
2
1
2
4x Washers
4x Lid Screws
5
1x Anti Tamper Shroud
4 Disconnect Aerial Fly Lead
Carefully remove the Aerial Fly Lead push on connector,
ensuring excessive strain is not placed on the lead or
connections.
6 Fix to the Wall
POWER
FAULT
All four circled fixing positions are
available for use.
FAULT
Ensure that the supplied washers
are fitted to all four fixing positions,
POWER IN
24V DC
as shown below.
-
+
RNC Back Back Box
Pre fitted screw insulator
Washer (fits over screw insulator)
Page 1 of 2
Product Description
Radio Network Communicator
3
4
3
1x RNC Lid
6
1x RNC Aerial
RESET
UP
BACK
ENTER
DOWN
POWER
FAULT
NETWORK
FAULT
POWER IN
24Vdc
-
+
TSD055 Iss 7 16/01/2018
5
6
7
4
1x RNC Back Box
7
2x Thumb Nuts
RESET
RS485
RS485
IN
OUT
+
-
+
-
UP
BACK
ENTER
DOWN
RS485
RS485
IN
OUT
+
-
+
-