1 Pre installation
Installation must conform to applicable local installation
!
codes and should only be installed by a fully trained
competent person.
Ensure the RNC is installed as per the site survey.
Refer to step 3 to ensure optimised wireless performance.
This device contains electronics that may be susceptible to
damage from Electrostatic Discharge (ESD). Take appropriate
precautions when handling electronic boards.
3 Mounting location guidelines
For optimum wireless
p e r f o r m a n c e , t h e
following
must
observed:
Ensure the RNC is not installed
within 2 m of other wireless or
electrical equipment (including
the Taktis control panel)
The RNC's aerial must not be
installed within 0.6 m of any
metal work.
5 Remove cable entry points
Drill the cable entry points as
necessary.
= DO NOT use
= Available cable
entry points
©2022 EMS Ltd. All rights reserved.
Radio Network Communicator
FC-TAK-438
POWER
FAULT
NETWORK FAULT
2 m
be
0.6 m
RNC
Taktis
fire
panel
Part no
FC-TAK-438-001
2 Components
1
2
3
1
2
4x washers
4x lid screws
5
1x anti tamper shroud
4 Disconnect aerial fly lead
Carefully remove the aerial fly lead push on connector,
ensuring excessive strain is not placed on the lead or
connections.
6 Fix to the wall
POWER
FAULT
All four circled fixing positions are
available for use.
FAULT
Ensure that the supplied washers
are fitted to all four fixing positions,
POWER IN
24V DC
as shown below.
-
+
RNC back box
Pre fitted screw insulator
Washer (fits over screw insulator)
Page 1 of 2
Product description
Radio Network Communicator For Taktis
4
5
3
4
1x RNC lid
6
7
1x RNC aerial
RESET
UP
BACK
ENTER
DOWN
MK281-99 Iss 2 20/01/2022
6
7
1x RNC back box
2x thumb nuts
RS485
RS485
IN
OUT
+
-
+
-
AJM