8.3. DCE (Dry Contact) card

8.3.1. The pin assignments of 10-Pin Terminal:
1
2
3
4
1
UPS on Bypass mode (Bypass)
2
Utility Normal (Normal close contact)
3
Utility Normal (Normal open contact)
4
Inverter On
5
Battery Low
6
Battery Bad or abnormal
7
UPS Alarm
8
Common
9
Shutdown UPS positive(+) signal
10
Shutdown UPS negative(-) signal
8.3.2. The shutdown function will be activeated, after a +6~+25Vdc is put
between pin 9 and pin 10 for 5 seconds.
8.3.3. The capacity of each relay contact is 40Vdc/25mA.
8.3.4. Installation Position:Optional Slot.
8.3.5. Flexible signal output for N.C.(Normal Close) or N.O.(Normal Open)
contact by shorting pin1-2 or pin2-3 form JP1-5.
8.3.6. The shutdown function will be enabled in 1 minute after blackout occurs
if the pin1-2 of both CN1 and CN6 are shorted by cap. Or, the shutdown
function can only be enabled by pin9-10 of CN3 if the pin2-3 of both
CN1 and CN6 are shorted by cap.
4
5
6
7
8
9
48

8.4. SNMP Cards

8.4.1. SNMP/WEB card
10
8.4.1.1 For installation, please refer to the user's manual attached with the
8.4.1.2 Installation Position:Optional Slot
8.4.2. SNMP card of Megatec
8.4.2.1 For installation, please refer to the user's manual attached with the
8.4.2.2 Installation Position:Optional Slot
card.
card.
49