GE D60 Instruction Manual page 663

Ur series line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 33 of 77)
ADDR
REGISTER NAME
6304
Negative Sequence Time Overcurrent 1 Multiplier
6305
Negative Sequence Time Overcurrent 1 Reset
6306
Negative Sequence Time Overcurrent 1 Block
6308
Negative Sequence Time Overcurrent 1 Target
6309
Negative Sequence Time Overcurrent 1 Events
630A
Reserved (7 items)
6311
...Repeated for Negative Sequence Time Overcurrent 2
Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 Modules)
63C0
Negative Sequence Instantaneous OC 1 Function
63C1
Negative Sequence Instantaneous OC 1 Signal Source
63C2
Negative Sequence Instantaneous Overcurrent 1 Pickup
63C3
Negative Sequence Instantaneous Overcurrent 1 Delay
63C4
Negative Sequence Instantaneous OC 1 Reset Delay
63C5
Negative Sequence Instantaneous Overcurrent 1 Block
63C7
Negative Sequence Instantaneous Overcurrent 1 Target
63C8
Negative Sequence Instantaneous Overcurrent 1 Events
63C9
Reserved (8 items)
63D1
...Repeated for Negative Sequence Instantaneous OC 2
Negative Sequence Overvoltage (Read/Write Grouped Setting) (3 Modules)
6440
Negative Sequence Overvoltage Function
6441
Negative Sequence Overvoltage Source
6442
Negative Sequence Overvoltage Pickup
6443
Negative Sequence Overvoltage Pickup Delay
6444
Negative Sequence Overvoltage Reset Delay
6445
Negative Sequence Overvoltage Block
6447
Negative Sequence Overvoltage Target
6448
Negative Sequence Overvoltage Events
6449
...Repeated for module number 2
6452
...Repeated for module number 3
Overfrequency (Read/Write Setting) (4 Modules)
6470
Overfrequency 1 Function
6471
Overfrequency 1 Block
6473
Overfrequency 1 Source
6474
Overfrequency 1 Pickup
6475
Overfrequency 1 Pickup Delay
6476
Overfrequency 1 Reset Delay
6477
Overfrequency 1 Target
6478
Overfrequency 1 Events
6479
Reserved (4 items)
647D
...Repeated for Overfrequency 2
648A
...Repeated for Overfrequency 3
6497
...Repeated for Overfrequency 4
Power Swing Detect (Read/Write Grouped Setting)
65C0
Power Swing Detect Function
65C1
Power Swing Detect Source
65C2
Power Swing Detect Mode
65C3
Power Swing Detect Supervision
65C4
Power Swing Detect Forward Reach
65C5
Power Swing Detect Forward RCA
65C6
Power Swing Detect Reverse Reach
65C7
Power Swing Detect Reverse RCA
65C8
Power Swing Detect Outer Limit Angle
65C9
Power Swing Detect Middle Limit Angle
65CA
Power Swing Detect Inner Limit Angle
GE Multilin
RANGE
0 to 600
0 to 1
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 30
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1.25
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 4294967295
0 to 5
20 to 65
0 to 65.535
0 to 65.535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1
0.05 to 30
0.1 to 500
40 to 90
0.1 to 500
40 to 90
40 to 140
40 to 140
40 to 140
D60 Line Distance Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
0.01
F001
---
1
F104
0 (Instantaneous)
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F167
Hz
0.01
F001
s
0.001
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F513
pu
0.001
F001
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
degrees
1
F001
degrees
1
F001
degrees
1
F001
DEFAULT
100
0
0 (Self-reset)
0 (Disabled)
B
0
0 (Disabled)
0 (SRC 1)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
300
50
50
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0 (SRC 1)
6050
500
500
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (Two Step)
600
5000
75
5000
75
120
90
60
B-41