GE D60 Instruction Manual page 473

Ur series line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5 SETTINGS
h) DIRECTIONAL COMPARISON BLOCKING1

PATH: SETTINGS
CONTROL ELEMENTS
 BLOCKING1 SCHEME
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin


PILOT SCHEMES
BLOCKING1 SCHEME
BLOCKING1 SCHEME
FUNCTION: Disabled
BLOCK1 SCHEME BLOCK:
Off
BLOCK1 RX CO-ORD PKP
DELAY: 0.010 s
TRANS BLOCK1 PICKUP
DELAY: 0.030 s
TRANS BLOCK1 RESET
DELAY: 0.090 s
BLOCK1 SCHEME SEAL-IN
DELAY: 0.010 s
BLK1 SCHME DIR FWD1:
Off
BLK1 SCHME DIR FWD2:
Off
BLK1 SCHME DIR FWD3:
Off
BLK1 SCHME DIR REV1:
Off
BLK1 SCHME DIR REV2:
Off
BLK1 SCHME DIR REV3:
Off
BLK1 FORCE TX STOP1:
Off
BLK1 FORCE TX STOP2:
Off
BLOCK1 SCHEME NO OF
COMM BITS: 1
BLOCK1 SCHEME RX1:
Off
BLOCK1 SCHEME RX2:
Off
BLOCK1 SCHEME RX3:
Off
BLOCK1 SCHEME RX4:
Off
BLOCK1 SCHEME TARGET:
Self-Reset
BLOCK1 SCHEME EVENTS:
Disabled
D60 Line Distance Protection System
5.7 CONTROL ELEMENTS
Range: Disabled, Enabled
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 1, 2, or 4
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
5
5-339

Advertisement

Table of Contents
loading

Table of Contents