5 SETTINGS
f) HYBRID PERMISSIVE OVER-REACHING TRANSFER TRIP

PATH: SETTINGS
CONTROL ELEMENTS
 HYBRID POTT SCHEME
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin


PILOT SCHEMES
HYBRID POTT SCHEME
HYB POTT SCHEME
FUNCTION: Disabled
HYB POTT BLOCK:
Off
HYB POTT PERMISSIVE
ECHO: Disabled
HYB POTT ECHO COND:
Off
HYB POTT WEAK
INFEED: Enabled
HYB POTT W/I COND:
Off
HYB POTT RX PICKUP
DELAY: 0.000 s
TRANS BLOCK PICKUP
DELAY: 0.020 s
TRANS BLOCK RESET
DELAY: 0.090 s
ECHO DURATION:
0.100 s
ECHO LOCKOUT:
0.250 s
HYB POTT SEAL-IN
DELAY: 0.010 s
GND DIR O/C FWD:
Off
GND DIR O/C REV:
Off
HYB POTT NO OF COMM
BITS: 1
HYB POTT RX1:
Off
HYB POTT RX2:
Off
HYB POTT RX3:
Off
HYB POTT RX4:
Off
HYB POTT SCHEME
TARGET: Self-Reset
HYB POTT EVENT:
Disabled
D60 Line Distance Protection System
5.7 CONTROL ELEMENTS
Range: Disabled, Enabled
Range: FlexLogic operand
Range: Disabled, Enabled, Custom
Range: FlexLogic operand
Range: Disabled, Enabled, Custom
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: FlexLogic operand
Range: 1, 2, or 4
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
5