GE D60 Instruction Manual page 463

Ur series line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5 SETTINGS
e) PERMISSIVE OVER-REACHING TRANSFER TRIP (POTT1)

PATH: SETTINGS
CONTROL ELEMENTS
 POTT1 SCHEME
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin


PILOT SCHEMES
POTT1 SCHEME
POTT1 SCHEME
FUNCTION: Disabled
POTT1 SCHEME BLOCK:
Off
POTT1 PERMISSIVE
ECHO: Disabled
POTT1 ECHO COND:
Off
POTT1 RX PICKUP
DELAY: 0.000 s
TRANS BLOCK PICKUP
DELAY: 0.020 s
TRANS BLOCK RESET
DELAY: 0.090 s
ECHO DURATION:
0.100 s
ECHO LOCKOUT:
0.250 s
LINE END OPEN PICKUP
DELAY:
0.050 s
POTT1 SEAL-IN
DELAY:
0.010 s
DIR FWD1:
Off
DIR FWD2:
Off
DIR FWD3:
Off
POTT1 NO OF COMM
BITS: 1
POTT1 RX1:
Off
POTT1 RX2:
Off
POTT1 RX3:
Off
POTT1 RX4:
Off
POTT1 SCHEME TARGET:
Self-Reset
POTT1 SCHEME EVENTS:
Disabled
D60 Line Distance Protection System
5.7 CONTROL ELEMENTS
Range: Disabled, Enabled
Range: FlexLogic operand
Range: Disabled, Enabled, Custom
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 1, 2, or 4
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
5
5-329