Power Supply - GE D60 Instruction Manual

Ur series line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
AC VOLTAGE
VT rated secondary:
50.0 to 240.0 V
VT ratio:
1.00 to 24000.00
Relay burden:
< 0.25 VA at 120 V
Conversion range:
1 to 275 V
Voltage withstand:
continuous at 260 V to neutral
1 min/hr at 420 V to neutral
FREQUENCY
Nominal frequency setting:25 to 60 Hz
Sampling frequency:
64 samples per power cycle
Tracking frequency range:20 to 65 Hz
CONTACT INPUTS
1000  maximum
Dry contacts:
Wet contacts:
300 V DC maximum
Selectable thresholds:
17 V, 33 V, 84 V, 166 V
Tolerance:
±10%
Contacts per common return: 4
Recognition time:
< 1 ms
Debounce time:
0.0 to 16.0 ms in steps of 0.5
Continuous current draw:4 mA (when energized)
CONTACT INPUTS WITH AUTO-BURNISHING
1000  maximum
Dry contacts:
Wet contacts:
300 V DC maximum
Selectable thresholds:
17 V, 33 V, 84 V, 166 V
Tolerance:
±10%
Contacts per common return: 2
Recognition time:
< 1 ms
Debounce time:
0.0 to 16.0 ms in steps of 0.5
Continuous current draw:4 mA (when energized)
Auto-burnish impulse current: 50 to 70 mA
Duration of auto-burnish impulse: 25 to 50 ms
DCMA INPUTS
Current input (mA DC): 0 to –1, 0 to +1, –1 to +1, 0 to 5, 0 to 10,
0 to 20, 4 to 20 (programmable)
379 ±10%
Input impedance:
Conversion range:
–1 to + 20 mA DC
Accuracy:
±0.2% of full scale
Type:
Passive
LOW RANGE
Nominal DC voltage:
24 to 48 V
Minimum DC voltage:
20 V
Maximum DC voltage:
60 V for RL power supply module, 75 V
for SL power supply module
Voltage loss hold-up:
200 ms duration at maximum load
NOTE: Low range is DC only.
ALL RANGES
2  Highest Nominal Voltage for 10 ms
Volt withstand:
Power consumption:
typical = 15 to 20 W/VA
maximum = 45 W/VA
GE Multilin
RTD INPUTS
Types (3-wire):
Sensing current:
Range:
Accuracy:
Isolation:
IRIG-B INPUT
Amplitude modulation:
DC shift:
Input impedance:
Isolation:
REMOTE INPUTS (IEC 61850 GSSE/GOOSE)
Input points:
Remote devices:
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Remote DPS inputs:
DIRECT INPUTS
Input points:
Remote devices:
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration:
Data rate:
CRC:
CRC alarm:
Responding to:
Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold:
Unreturned message alarm:
Responding to:
Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold:
TELEPROTECTION
Input points:
Remote devices:
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration:
Data rate:
CRC:
HIGH RANGE
Nominal DC voltage:
Minimum DC voltage:
Maximum DC voltage:
Nominal AC voltage:
Minimum AC voltage:
Maximum AC voltage:
Voltage loss hold-up:
D60 Line Distance Protection System
2.3 SPECIFICATIONS
100 Platinum, 100 & 120 Nickel, 10
Copper
5 mA
–50 to +250°C
±2°C
36 V pk-pk
1 to 10 V pk-pk
TTL–Compatible
50 k
2 kV
32, configured from 64 incoming bit pairs
16
5
32
16
Yes, No
64 or 128 kbps
32-bit
Rate of messages failing the CRC
1 to 1000 in steps of 1
Rate of unreturned messages in the ring
configuration
1 to 1000 in steps of 1
16
3
No
64 or 128 kbps
32-bit

2.3.6 POWER SUPPLY

125 to 250 V
88 V
300 V
100 to 240 V at 50/60 Hz
88 V at 25 to 100 Hz
265 V at 25 to 100 Hz
200 ms duration at maximum load
contact factory for exact order code con-
sumption