Transducer Inputs/Outputs - GE D60 Instruction Manual

Ur series line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

3 HARDWARE
The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, check the auto-
burnish functionality using an oscilloscope.
NOTE
Transducer input modules can receive input signals from external DCmA output transducers (DCmA In) or resistance tem-
perature detectors (RTDs). Hardware and software are provided to receive signals from these external transducers and
convert these signals into a digital format for use as required.
Transducer output modules provide DC current outputs in several standard DCmA ranges. Software is provided to config-
ure virtually any analog quantity used in the relay to drive the analog outputs.
Every transducer input/output module has a total of 24 terminal connections. These connections are arranged as three ter-
minals per row with a total of eight rows. A given row can be used for either inputs or outputs, with terminals in column "a"
having positive polarity and terminals in column "c" having negative polarity. Since an entire row is used for a single input/
output channel, the name of the channel is assigned using the module slot position and row number.
Each module also requires that a connection from an external ground bus be made to terminal 8b. The current outputs
require a twisted-pair shielded cable, where the shield is grounded at one end only. The following figure illustrates the trans-
ducer module types (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay.
Wherever a tilde "~" symbol appears, substitute with the slot position of the module.
NOTE
Figure 3–20: TRANSDUCER INPUT/OUTPUT MODULE WIRING
The following figure show how to connect RTDs.
GE Multilin
D60 Line Distance Protection System
3.2 WIRING

3.2.7 TRANSDUCER INPUTS/OUTPUTS

3
3-19

Advertisement

Table of Contents
loading

Table of Contents